Power Auto-transformer Mechanical Faults Diagnosis Using Finite Element based FRA
نویسندگان
چکیده مقاله:
Frequency response analysis (FRA) is a sensitive method established for testing the mechanical integrity of transformers. However, interpretation of FRA signature still needs expert opinions and there is no FRA interpretation code generally accepted. Various mechanical faults with different extents on power transformers are required to aid FRA interpretation. To address this challenge, in this paper a high definition 3D FEM model of a three-phase, three-winding, 125-MVA power auto-transformer was constructed using finite element method and verified by experimental FRA measurements. Various radial deformations and axial displacements were formed using FEM model and the extracted parameters of the winding detailed model were used to obtain power transformer frequency responses. The commonly used appropriate statistical indices in FRA diagnosis were utilized for interpreting FRA results. The study showed that the frequency range between 1-100 kHz is mainly affected by the mechanical faults and the 1st resonance of the double-peak feature of the auto-transformer FRA remains unchanged during winding radial deformation and axial displacement.
منابع مشابه
Power Transformer Incipient Faults Diagnosis Based on Dissolved Gas Analysis
Incipient fault diagnosis of a power transformer is greatly influenced by the condition assessment of its insulation system oil and/or paper insulation. Dissolved gas-in-oil analysis (DGA) is one of the most powerfull techniques for the detection of incipient fault condition within oil-immersed transformers. The transformer data has been analyzed using key gases, Doernenburg, Roger, IEC and Duv...
متن کاملPower Transformer Incipient Faults Monitoring
Power transformers are important and expensive components in the electric power system. The knowledge of the actual status of the transformer insulation behavior, load tap changer performance, temperature, and load condition is necessary in order to evaluate the service performance concerning reliability, availability and safety. Systems abnormalities, loading, switching and ambient condition n...
متن کاملCharacterization of Power Transformer Electromagnetic Forces Affected by Winding Faults
Electromagnetic forces in power transformer windings are produced by interaction between the leakage fluxes and current passing them. Since the leakage flux distribution along the windings height is in two axial and radial directions, so the electromagnetic forces have two components, radial and axial. There is a risk that a large electromagnetic force due to the short circuit or inrush current...
متن کاملDiagnosis of Power Transformer Faults based on Five Fuzzy Ratio Method
Dissolved Gas Analysis is one of the most useful method to detect incipient faults in transformer. Amongst the conventional DGA methods, IEC three ratio method is widely used. One of the disadvantages in its present form is that a significant number of DGA results inservice fall outside the existing IEC codes and cannot be diagnosed. To overcome this limitation, additional eighteen new combinat...
متن کاملArtificial Intelligence Based Approach for Identification of Current Transformer Saturation from Faults in Power Transformers
Protection systems have vital role in network reliability in short circuit mode and proper operating for relays. Current transformer often in transient and saturation under short circuit mode causes mal-operation of relays which will have undesirable effects. Therefore, proper and quick identification of Current transformer saturation is so important. In this paper, an Artificial Neural Network...
متن کاملHottest Spot and Life Evaluation of Power Transformer Design Using Finite Element Method
Power transformers represent the largest portion of capital investment in transmission and distribution substations. In addition, power transformer outages have a considerable economic impact on the operation of an electrical network. One of the most important parameters’ governing a transformer’s life expectancy is the hot-spot temperature value. Due to under estimation of stray losses in powe...
متن کاملمنابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
ذخیره در منابع من قبلا به منابع من ذحیره شده{@ msg_add @}
عنوان ژورنال
دوره 08 شماره 01
صفحات 31- 38
تاریخ انتشار 2019-03-01
با دنبال کردن یک ژورنال هنگامی که شماره جدید این ژورنال منتشر می شود به شما از طریق ایمیل اطلاع داده می شود.
میزبانی شده توسط پلتفرم ابری doprax.com
copyright © 2015-2023