Estimation of Moisture in Transformer Insulation Using Dielectric Frequency Response Analysis by Heuristic Algorithms
نویسندگان
چکیده مقاله:
Transformers are one of the most valuable assets of power systems. Maintenance and condition assessment of transformers has become one of the concerns of researchers due to huge number of transformers has been approached to the end of their lifetimes. Transformer’s lifetime depends on the life of its insulation and the insulation’s life is strongly influenced by its moisture attraction as well. Thus, regarding to the importance of moisture analysis, in this paper a new method is introduced for the moisture content determination in the transformer insulation system. The introduced method uses the dielectric response analysis in the frequency domain based on heuristic algorithms such as genetic algorithm and particle swarm optimization. First, the master curve of the dielectric response is modeled. Afterwards, using the proposed method the master curve and the measured dielectric response curves are compared. By analyzing the comparison results, the moisture content of the paper insulation, electrical conductivity of the insulating oil and the dielectric model dimensions are determined. Finally, the proposed methods are applied to several practical samples and their capabilities are compared to the well-known conventional method.
منابع مشابه
Determination of Moisture Content in Mass Impregnated Cable Insulation Using Low Frequency Dielectric Spectroscopy
The variations in the low frequency dielectric spectra of mass impregnated insulation depending on its moisture content have been investigated. For the calibration purposes a number of the impregnated paper samples was kept in the desiccators where different relative humidities were maintained. Thus obtained moisture content in the samples ranged from 1 % up to 6 %. The variations of the comple...
متن کاملTransformer Fault Detection Using Frequency Response Analysis
Power transformers prove to be a vital element or tool in electrical power supply and transmission system. They are capital intensive units and need to be monitored for faults. Faults in transformers leading to their failure are repugnant. Thus, there is a need to detect such faults at an initial level. This paper aims to detect, diagnose the nature and cause of mechanical faults, their identit...
متن کاملAnalysis transformer insulation by PDC method
Paragraph is about mathematical interpretation of transformer insulation system. Base of this system is composed by two elements oil and paper. We need to simulate this system for more precisely results from measurement. Section three describes how to calculate relaxation currents and how that currents are generated. So we are able to compare measured and computed values and deduce actual condi...
متن کاملImproved Moisture Analysis of Power Transformers Using Dielectric Response Methods
This paper starts with a systematic benchmark test of the three commercialised dielectric diagnostic methods RVM (recovery voltage method), PDC (polarisation and depolarisation currents) and FDS (frequency domain spectroscopy), performed on a large transformer model. Starting from the explored strengths and weaknesses a more sophisticated instrument with corresponding software was developed. Th...
متن کاملMeasurement Error Estimation for Capacitive Voltage Transformer by Insulation Parameters
Measurement errors of a capacitive voltage transformer (CVT) are relevant to its equivalent parameters for which its capacitive divider contributes the most. In daily operation, dielectric aging, moisture, dielectric breakdown, etc., it will exert mixing effects on a capacitive divider’s insulation characteristics, leading to fluctuation in equivalent parameters which result in the measurement ...
متن کاملInvestigating the impacts of ageing and moisture on dielectric response of oil/paper insulation systems
The oil/paper insulation system in a transformer degrades under various chemical, thermal and electromechanical stresses during its operation. Dielectric response measurements like the Return Voltage Measurement (RVM) and Polarisation and Depolarisation Current (PDC) measurement are currently being used for condition assessment of the insulation. In the current research project, the ageing cond...
متن کاملمنابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید