Considering Pilot Protection in the Optimal Coordination of Distance and Directional Overcurrent Relays
Authors
Abstract:
The aim of the relay coordination is that protection systems detect and isolate the faulted part as fast and selective as possible. On the other hand, in order to reduce the fault clearing time, distance protection relays are usually equipped with pilot protection schemes. Such schemes can be considered in the distance and directional overcurrent relays (D&DOCRs) coordination to achieve faster protection systems, while the selectivity is maintained. Therefore, in this paper, a new formulation is presented for the relay coordination problem considering pilot protection. In the proposed formulation, the selectivity constraints for the primary distance and backup overcurrent relays are defined based on the fault at the end of the transmission lines, rather than those at the end of the first zone of the primary distance relay. To solve this nonlinear optimization problem, a combination of genetic algorithm (GA) and linear programming (LP) is used as a hybrid genetic algorithm (HGA). The proposed approach is tested on an 8-bus and the IEEE 14-bus test systems. Simulation results indicate that considering the pilot protection in the D&DOCRS coordination, not only obtains feasible and effective solutions for the relay settings, but also reduces the overall operating time of the protection system.
similar resources
Optimal Coordination of Distance and Directional Overcurrent Relays Considering Different Network Topologies
Most studies in relay coordination have focused solely on coordination of overcurrent relays while distance relays are used as the main protection of transmission lines. Since, simultaneous coordination of these two types of relays can provide a better protection, in this paper, a new approach is proposed for simultaneous coordination of distance and directional overcurrent relays (D&DOCRs). Al...
full textEfficient Dimensionality Reduction of Directional Overcurrent Relays Optimal Coordination Problem
Directional over current relays (DOCR) are commonly used in power system protection as a primary protection in distribution and sub-transmission electrical systems and as a secondary protection in transmission systems. Coordination of protective relays is necessary to obtain selective tripping. In this paper, an approach for efficiency reduction of DOCRs nonlinear optimum coordination (OC) is p...
full textA Novel Objective Function for Directional Overcurrent Relays Coordination
Directional overcurrent relays (DOCRs) are widely used to protect power systems. For optimal coordination of DOCRs, several techniques have been proposed to solve this problem. A common way of optimal coordination of DOCRs is using evolutionary algorithms such as genetic algorithm (GA). In this paper, a novel strategy for DOCRs coordination is proposed. In the proposed strategy, a new objective...
full textDirectional Overcurrent Relays Coordination Problems in Distributed Generation Systems
This paper proposes a new approach to the distributed generation system protection coordination based on directional overcurrent protections with inverse-time characteristics. The key question of protection coordination is the determination of correct values of all inverse-time characteristics coefficients. The coefficients must be correctly chosen considering the sufficiently short tripping ti...
full textهماهنگی بهینه رله های اضافه جریان جهتی در شبکه های توزیع با در نظر گرفتن پایداری گذرای منابع تولید پراکنده سنکرون
Integration of distributed generation (DG) into distribution networks causes some protection challenges, which can be solved by appropriate coordination of directional overcurrent relays. The optimal coordination of directional overcurrent relays is an important task to fulfill the protection requirements of the network. This paper presents an optimal coordination method for directional overcur...
full textOptimal Coordination of Directional Overcurrent Relays using Particle Swarm Optimization Technique
The main function of the protective devices in the power system is to detect and remove the selected faulty parts as fast as possible. Directional over current relays are commonly used for the protection of interconnected sub transmission systems, distribution systems, or as a secondary protection of transmission systems. For the systems having more than one source connected, that is meshed or ...
full textMy Resources
Journal title
volume 11 issue 2
pages 154- 164
publication date 2015-06
By following a journal you will be notified via email when a new issue of this journal is published.