Crowds Flow Detection and Indoor Temperature Monitoring for Advanced Air-conditioning Control

نویسندگان

  • Kyoichiro KATABIRA
  • Huijing ZHAO
  • Ryosuke SHIBASAKI
  • Masatoshi SEKINE
  • Kaoru SEZAKI
چکیده

In this paper, we propose a novel air-conditioning system that will be effective for wide public space such as a concourse of railway station, exhibition hall or museum. In these spaces, conventional air-conditioners are not enough, since the air-conditioner sends a wind to also empty area and where the temperature is already sufficient. Generally, it is difficult to ventilate effectively to the extensive coverage. On the other hand, our proposed system monitors people-flow and temperature distribution simultaneously, so that the system detects an optimum location to send a cool/warm wind, i.e. where the population density is relatively high and the temperature is insufficient. In order to track a number of pedestrians, we exploit multiple laser range scanners, since they are not only independent from lighting condition, but also can measure a range data directly with wider coverage. Additionally, we attempt to extract a crowds-flow or stream of confluences within lots of trajectories. This approach has seldom researched. While, by using wireless sensor network technology, a temperature distribution in the target space is calculated with IDW spatial interpolation. Finally, by integrating these two types of information, crowds-flows and temperature distribution, the proposed system detects a position where should be fan, and then, it controls the nozzle’s orientation on the real-time basis. The availability is tested by conducting an experiment at railway station in Japan. By applying the proposed system, a ventilator can aim at more persons for longer period to fan each person than conventional air-conditioning system.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Design and operation optimization of an air conditioning system through simulation: an hour-by-hour simulation study

In the present research, performance validation of a Heating, Ventilation, and Air Conditioning (HVAC) system operating in a library building was conducted. The operating HVAC system was studied in terms of the provided indoor air conditions and energy consumption level. The fieldwork measurements showed that the HVAC system is not capable of providing the desired indoor air conditions based on...

متن کامل

Implementation of adaptive indoor comfort temperature control via embedded system for air-conditioning unit

Environmental control strategy via computerized implementation is one of the most efficient approaches to integrate new advanced knowledge in research of human thermal comfort to a mechanical air-conditioning unit. Recently, a new conceptual development in designing air-conditioning systems has indicated that the indoor comfort temperature strongly depends upon changes of the outdoor air temper...

متن کامل

A PD Law Based Fuzzy Logic Control Strategy For Simultaneous Control Of Indoor Temperature And Humidity Using A Variable Speed Direct Expansion Air Conditioner

In small to medium scale buildings located in the subtropics, such as Hong Kong, direct expansion air conditioning (DX A/C) systems are widely applied. This is because, as compared to chilled water based central air conditioning systems, DX A/C systems are compact, flexible for multi-room services, energy efficient and cost less to maintain and operate. However, traditionally, a DX A/C system i...

متن کامل

Flow Analysis Heat and Mass Transfer in a Room

This reports the study on the flow behaviour, heat transfer and contamination distribution in a room. For this purpose the 3-D incompressible Navier-Stokes equations, energy equation and a mass transfer equation which model the concentration of contamination have been applied. For turbulence simulation the two equation standard k-  turbulence model was employed. By means of SIMPLE algorithm the...

متن کامل

Design of Air Distribution System for Operation Theatre Using Flow Visualization Techniques to Improve Flow Characteristics

Operation Theatre (OT) is the most important area where precise controlled on indoor air quality is required because it is directly related to patient health and its recovery period. This work aims to study and visualize the airflow distribution of conventional flat air diffuser ventilation system and newly designed angular air ventilation system in OT. Angular Air Distribution (AAD) system is ...