Two - Level Dissolved Oxygen Control for Activated Sludge Processes
نویسندگان
چکیده
Two-level controllers for dissolved oxygen reference trajectory tracking for activated sludge processes is proposed and investigated. Both the nutrient and the phosphorous removal from a wastewater by its biological treatment using an activated sludge technology are considered. Typically, an aeration system itself is a complicated hybrid nonlinear dynamical system with faster dynamics compared to internal dynamics of the dissolved oxygen at a biological reactor. It is common approach to neglect this dynamics and also important operational limitations of this system such as a limited frequency of allowed switching of the blowers. The paper proposes a two level controller to track prescribed dissolved oxygen trajectory. The upper level control unit produces desired aeration flow set points. For this unit the aeration system is an actuator. The nonlinear model predictive control algorithm is applied to design this controller unit. Also, the predictive control is used to design the lower level control unit based on a linearised hybrid dynamics of the aeration process. The overall controller is validated by simulation using real data sets and ASM2d model of the biological reactor.
منابع مشابه
Dissolved oxygen control of the activated sludge wastewater treatment process using model predictive control
Activated sludge wastewater treatment processes are difficult to be controlled because of their complex and nonlinear behavior, however, he control of the dissolved oxygen level in the reactors plays an important role in the operation of the facility. For this reason a new pproach is studied in this paper using simulated case-study approach: model predictive control (MPC) has been applied to co...
متن کاملHierarchical dissolved oxygen control for activated sludge processes
A hierarchical controller for tracking the dissolved oxygen (DO) reference trajectory in activated sludge processes is proposed and investigated. The removal of nitrogen and phosphorous from wastewater is considered. Typically, an aeration system itself is a complicated hybrid nonlinear dynamical system with faster dynamics compared to the internal dynamics of the DO in a biological reactor. It...
متن کاملImprovements in Modelling Dissolved Oxygen in Activated Sludge Systems
The aim of this research was to show the impact of the flow conditions and variations in the aeration intensity on changes in the predicted dissolved oxygen (DO) concentrations in a full-scale activated sludge reactor. The Activated Sludge Model No. 1 was used to describe the biochemical processes. The studies were performed at the Rock Creek wastewater treatment plant in Hillsboro, OR (USA). T...
متن کاملSupervisory Control System for Adaptive Phase and Work Cycle Management of Sequencing Wastewater Treatment Plant
The paper presents the design of the integrated control system applied to Sequencing Batch Reactor (SBR) in a biological Wastewater Treatment Plant (WWTP) in Swarzewo, which operates under activated sludge technology. Based on the real data records, ASM2d biological processes model and aeration system model, hierarchical control system for dissolved oxygen tracking and cycle management is desig...
متن کاملNonlinear fuzzy Control System for dissolved oxygen with aeration System in sequencing batch reactor
Biological processes at a wastewater treatment plant are complex, multivariable, time varying and nonlinear. Moreover, interactions between the components are very strong. Control of dissolved oxygen is one of most important task at the plant. The level of dissolved oxygen in aerobic tanks has significant influence on behaviour and activity of microorganisms at the plant. Air for aerated tanks ...
متن کامل