A Simple Harmonics Based Stiction Detection Method
نویسندگان
چکیده
Oscillation or large variability of the control loops results decreased economical advantage to process industries due to inferior quality products, larger rate of rejections, reduced average throughputs and overall increased energy requirements. Stiction is one of the root cause of oscillation. Many studies suggest that 30% of the control loops are oscillatory because of control valve problems such as stiction, deadband and hysteresis. In this study, a simple method has been developed to detect stiction. It has been shown that stiction in control valves produces signals containing odd harmonics. The proposed method estimates frequencies and amplitudes of control error signal using least square method. Then, harmonic relation among the frequencies are examined. The presence of odd harmonics indicates valve stiction. The method has been evaluated successfully using simulated, experimental and industrial data sets.
منابع مشابه
Novel Closed-loop Stiction Detection and Quantification Method via System Identification
In this paper, a novel detection and quantification method of control valve stiction is discussed. A time delay estimation method is presented for processes under an oscillating state. A suitable model structure of valve stiction is chosen prior to conducting valve stiction detection and quantification. Given the stiction model structure, a bounded search space of a stiction model is defined an...
متن کاملA Single Curve Piecewise Fitting Method for Detecting Valve Stiction and Quantification in Oscillating Control Loops
Stiction is one of the most common problems in the spring-diaphragm type control valves, which are widely used in the process industry. In this paper, a procedure for single curve piecewise fitting stiction detection method and quantifying valve stiction in control loops based on ant colony optimization has been proposed. The single curve piecewise fitting method of detecting valve stiction is ...
متن کاملA segmentation-based approach for detection of stiction in control valves
A method for detecting static friction (stiction) in control valves is proposed. The method is model-based and is inspired by ideas from the fields of change detection and multi-model mode estimation. Opposed to existing methods only limited process knowledge is needed and it is not required that the loop has oscillating behavior. The advantage of the method is illustrated in both numerical sim...
متن کاملPractical Model and Detection Algorithm for Valve Stiction
Stiction is the most common problem in pneumatic control valves, which are widely used in the process industry. Stiction causes fluctuation of process variables, which lowers productivity. Therefore, developing a method to detect stiction and distinguish it from other causes is crucial to help operators take an appropriate action for improving control performance. The present work proposes a va...
متن کاملStiction identification in nonlinear process control loops
Nearly 20-30% of all process control loops oscillate due to stiction and lead to loss of productivity. Thus, the detection and quantification of stiction in control valves using just the raw operating data is an important component of any automated controller performance monitoring application. Many techniques have been proposed for the detection and quantification of stiction. Pattern based id...