Comparison between Model- and pH/ORP- Based Process Control for an AAA System
نویسندگان
چکیده
Model-based and on-line sensor control schemes in an alternating aerobic/anoxic system for nitrogen removal were applied and compared for system performance. A linear model was developed by simplifying the well known Activated Sludge Model No. 1 and incorporated into an optimization scheme. A program was developed to detect control points on the pH and ORP profiles to control aeration duration in an alternating system. Both systems demonstrate good COD (85%) and nitrogen (76-80%) removal efficiencies, with a range of the aeration ratio (aeration cycle time/total cycle time) 0.23 to 0.3. Both systems could save significant aeration energy, in addition to handling the variation of influent nitrogen loading. The model-based optimization approach has some advantages over the pH and ORP sensor control scheme, since the effluent ammonia level can be set by an operator according to the effluent regulation. Conversely, the online sensor based control scheme can be easily applied into a real system, since it does not require calibration or measurements of influent compositions.
منابع مشابه
An ANOVA Based Analytical Dynamic Matrix Controller Tuning Procedure for FOPDT Models
Dynamic Matrix Control (DMC) is a widely used model predictive controller (MPC) in industrial plants. The successful implementation of DMC in practical applications requires a proper tuning of the controller. The available tuning procedures are mainly based on experience and empirical results. This paper develops an analytical tool for DMC tuning. It is based on the application of Analysis of V...
متن کاملRegulation of Denitrification Using Continually Measured ORP and pH Signal
The use of pH and oxidation-reduction potential (ORP) as control parameters for the nitrificationdenitrification process is compared and discussed. The signals were measured in a sequencing batch reactor activated sludge system and in a completely mixed activated sludge reactor. The termination of denitrification was clearly identified not only by an ORP signal, but also by a pH signal. However...
متن کاملA TS Fuzzy Model Derived from a Typical Multi-Layer Perceptron
In this paper, we introduce a Takagi-Sugeno (TS) fuzzy model which is derived from a typical Multi-Layer Perceptron Neural Network (MLP NN). At first, it is shown that the considered MLP NN can be interpreted as a variety of TS fuzzy model. It is discussed that the utilized Membership Function (MF) in such TS fuzzy model, despite its flexible structure, has some major restrictions. After modify...
متن کاملAdaptive Neuro Fuzzy Sliding Mode Based Genetic Algorithm Control System to Control of a pH Neutralization Process
In this paper, an adaptive neuro fuzzy sliding mode based genetic algorithm (ANFSGA) controlsystem is proposed for a pH neutralization system. In pH reactors, determination and control of pH isa common problem concerning chemical-based industrial processes due to the non-linearity observedin the titration curve. An ANFSGA control system is designed to overcome the complexity of precisecontrol o...
متن کاملInvestigation of Phasic Process of Biogas Yield by Measuring pH, ORP and Electrical Power Changes
Background & Aims of the Study: Studying the phasic process of the biogas yieldis required to optimize the design and operations; it also helps to lower energy production costs by decreasing the capital investment and operational costs. Here we determine the biogas process by measuring pH, ORP, electrical power and make compatibility to the biogas production trend. Materi...
متن کامل