The Influence of the Inlet Conditions on the Airside Heat Transfer Performance of Plain Finned Evaporator
ثبت نشده
چکیده
A numerical study has been conducted to investigate the influence of fin pitch and relative humidity on the heat transfer performance of the fin-and-tube heat exchangers having plain fin geometry under dehumidifying conditions. The analysis is done using the ratio between the heat transfer coefficients in totally wet conditions and those in totally dry conditions using the appropriate correlations for both dry and wet conditions. For a constant relative humidity, it is found that the heat transfer coefficient increases with the increase of the air frontal velocity. By contrast, the fin efficiency decreases when the face velocity is increased. Apparently, this phenomenon is attributed to the path of condensate drainage. For the influence of relative humidity, the results showed an increase in heat transfer performance and a decrease in wet fin efficiency when relative humidity increases. This is due to the higher amount of mass transfer encountered at higher relative humidity. However, it is found that the effect of fin pitch on the heat transfer performance depends strongly on the face velocity. At lower frontal velocity the heat transfer increases with fin pitch. Conversely, an increase in fin pitch gives lower heat transfer coefficients when air velocity is increased. Keywords—Dehumidifying conditions, Fin efficiency, Heat and mass transfer, Heat exchangers.
منابع مشابه
Heat and Mass Transfer Coefficients Under Frost Conditions In A Finned-Tube Evaporator
The objectives of this study are to provide experimental data and a correlation that can be used in the optimal design of an evaporator under frost conditions. In the present study, we tested both a single stage and a two-stage evaporator with a variation of operating parameters and fin geometry under frost conditions. The effects of tube space and fin alignment on the heat transfer performance...
متن کاملFull Analysis of Low Finned Tube Heat Exchangers
In this paper, first the governing parameters characterizing low-finned tubes are reviewed. Second, the more important of the available performance correlations are compared with the available experimental data. The most reliable one can be employed to develop a pressure drop relationship, which has already been used in an algorithm for exchanger sizing. Also a means for the identification of a...
متن کاملThe Impact of Fouling on the Performance of Filter-Evaporator Combinations
This paper presents results of experiments performed on 6 different combinations of filters and evaporator coils under clean and fouled conditions. The fouled conditions were obtained after injection of 600 grams of dust upstream of the filter/coil combination, which was meant to simulate a year of operation in the field. The airside pressure drops of the coils and filters and airside effective...
متن کاملPassive Energy Air-to-Water Heat Pipe Based Heat Exchanger and its Potential of Air Pre-cooling in Air Conditioning Systems for Iran Climate
Air pre-cooling equipment is normally being employed in air-conditioning systems for pre-cooling the ambient outdoor air to enhance the air-conditioning systems performance. In this study, the potential of a passive water-to-air heat pipe based heat exchanger (HPHEX) for air pre-cooling purpose in air-conditioning systems for the high cooling load demanding regions of Iran was investigated. To ...
متن کاملPii: S1359-4311(02)00194-1
The performance of two evaporatively cooled heat exchangers is investigated under similar operating conditions of air flow rates and inlet hot water temperatures. The heat exchangers are plain and plate-finned circular tube types which occupy the same volume. Spray water, which is circulated in a closed circuit, is injected onto the exposed surfaces of the tubes and fins. The contact between ai...
متن کامل