Negative Sequence Impedance Measurement for Distributed Generator Islanding Detection
نویسنده
چکیده
This thesis presents a method of detecting electrical islands in low voltage distributed generator networks by measuring negative sequence impedance differences between islanded and utility connections. Extensive testing was conducted on a commercial building and 25 kV distributed generator fed network by measuring naturally occurring and artificially injected negative sequence components. Similarly, this technique was tested using the IEEE 399-1990 bus test case using the EMTP software. The practical measurements have been matched to simulations where further system performance characteristics of detecting power system islands has been successfully demonstrated. Measured results indicate that unbalanced load conditions are naturally occurring and readily measurable while deliberately unbalanced loads can increase the accuracy of negative sequence impedance islanding detection. The typically low negative sequence impedance of induction motors was found to have only a small effect in low voltage busses, though large machines can effect the threshold settings. Careful placement of the island detector is required in these situations. The negative sequence impedance measurement method is an improvement on previous impedance measurement techniques for islanding detection due to its accuracy, and distinctly large threshold window which have challenged previous impedance based islanding detection techniques.
منابع مشابه
Inverter based distributed generator islanding detection method using U/O voltage relay
Islanded operation of distributed generators is a problem that can take place when they are connected to a distribution system. In this paper an islanding detection method is presented for inverter based distributed generation (DG) using under/over voltage relay. The method is an adaptive one and is based on the change of DG active power reference (Pref) in inverter control interface. The activ...
متن کاملIslanding Detection in Distributed Generations Using Negative Sequence Components
In this paper negative sequence components are used for islanding detection in distributed generation (DG) based system. In this approach, the negative sequence component of the voltage and current signals are analyzed through wavelet transform. The detailed coefficient d1 clearly identifies the event and thus detects the islanding condition. The change in energy and standard deviations of wave...
متن کاملIslanding Detection and Frequency Circuit Measurement by Power Distribution Relation Depending on the Angle
This paper presents a new islanding detection method based on the difference of the power transfer angle between the distributed generation and local load. After islanding, current id and iq will be changed by adding the variation to d_q transformation block of current. This makes voltage and frequency disturbance and therefore islanding is recognized. Active islanding detection method usually ...
متن کاملAlgorithm for islanding detection in distributed generation system
Power industry has been emphasizing more importance on distributed generation because there are new technology like fuel cell, wind turbine and power electronic use for advancement of power system has been evolved so much which cannot be possible without distributed generation. Hence distributed generation (DG) has become an inseparable part in power system and gained so much importance because...
متن کاملAn Intelligent Anti-Islanding Scheme for Synchronous-Based Distributed Generation Using Reduced-Noise Morphological Gradient
This paper presents a pattern recognition-based scheme for detection of islanding conditions in synchronous- based distributed generation (DG) systems. The main idea behind the proposed scheme is the use of spatial features of system parameters such as the frequency, magnitude of positive sequence voltage, etc. In this study, the system parameters sampled at the point of common coupling (PCC) w...
متن کامل