Simulation and Validation of a Two-Stage Flash Tank Cycle Using R410A as a Refrigerant
نویسندگان
چکیده
Investigating alternative system configurations is a means to improving vapor compression system COP by increasing system capacity and reducing compressor power consumption. The characterization and optimization of alternative system configurations can be conducted through the use of simulation. This paper presents a vapor compression system simulation tool capable of modeling a two-stage flash tank cycle. The key component model in the simulation of a two-stage flash tank cycle is the compressor. The component-based nature of the simulation tool allows for the use of any type of two-stage compressor model, including a vapor-injection compressor. The simulation assumptions and approach are presented in this paper. The experimental validation for both the baseline cycle and flash tank cycle are presented for an R410A system operating in both heating and cooling modes. A total of 52 test points were included in the validation for the two operating modes. The calculated capacity for 48 of the 52 test points was predicted to within 5% of experimental values.
منابع مشابه
Investigation of Vapor Injection Heat Pump System with a Flash
Title of Dissertation: INVESTIGATION OF VAPOR INJECTION HEAT PUMP SYSTEM WITH A FLASH TANK UTILIZING R410A AND LOW-GWP REFRIGERANT R32 Xing Xu, Doctor of Philosophy, 2012 Dissertation Directed by: Professor Reinhard Radermacher Department of Mechanical Engineering Vapor injection technique has proven to be effective in improving heat pump system performance, especially for cooling application a...
متن کاملControl Strategy of Vapor Injection Cycle
Vapor refrigerant injection cycle with a flash tank has proven to be effective in improving system performance significantly at extremely low and high ambient temperatures. However, the control strategy of operating the system is still unclear. There is no open publication on the comprehensive study of the vapor injection cycle control strategy to date. This paper presents the experimental inve...
متن کاملPerformance Investigation of Refrigerant Vapor-Injection Technique for Residential Heat Pump Systems
An 11 kW R410A heat pump system with a two-stage vapor-injected scroll compressor has been developed and tested. A conventional heat pump system with a scroll compressor having the same displacement volume to the vapor-injected scroll compressor has been tested under the same conditions to serve as a baseline. The vaporinjected scroll compressor has been tested with the cycle options of both fl...
متن کاملTechnologies to Improve the Performance of A/C Systems in Hot Climate Regions
Air conditioning contributes significantly to building energy consumption in hot climate regions. In addition to greater cooling requirements in hot climates, cooling equipment efficiency decreases with increasing outdoor temperature. Therefore, it is advantageous to develop improved technologies that can achieve higher efficiency at high ambient conditions. In this paper, two novel compression...
متن کاملStandardized Polynomials for Fast Evaluation of Refrigerant Thermophysical Properties
Steady state and dynamic simulation and optimization are a key step in the design of heating, ventilation, airconditioning and refrigeration (HVAC&R) systems. It is well known that the computation time in such simulations is dominated by the refrigerant thermophysical property calculations. These calculations generally involve calculating all thermophysical properties given one or two independe...
متن کامل