A Novel AE Based Algorithm for PD Localization in Power Transformers
نویسندگان
چکیده
In this paper, a novel algorithm for PD localization in power transformers based on wavelet de-noising technique and energy criterion is proposed. Partial discharge is one of the main failures in power transformers. The localization of which could be very useful for maintenance systems. Acoustic signals due to a PD event are transient, irregular and non-repetitive. So wavelet transform is an efficient tool for this signal processing problem that gives a time-frequency demonstration. First, different wavelet based de-noising methods are analyzed. Then, a reasonable structure for threshold value determining and applying manner on signals is presented. Evaluated errors are good evidences for choices. Next, applying the elimination low energy frequency bands is discussed and developed as a de-noising method. Time differences between signals are used for PD localization. Different ways in time arrival detection are introduced and a novel approach in energy criterion method is presented. At the end, the quality of algorithm is verified through the different assays in lab.
منابع مشابه
مدلسازی سیم پیچ ترانسفورماتورهای قدرت با استفاده از مدل خط انتقال چند سیمه بمنظور مکانیابی تخلیه جزئی
In this paper Multi conductor transmission line model (MTLM) was used for partial discharge (PD) localization in power transformers’ windings. The parameters of the model were computed considering practical issues of power transformer design. To decrease computational complexity of the model, two methods for calculation of model parameters were studied and the most suitable method was cho...
متن کاملEvaluating the Improvement of Partial Discharge Localization Accuracy Using Frequency Response Assurance Criterion
Partial Discharge (PD) is the most important source of insulation degradation in power transformers. In order to prevent catastrophic failures in transformers, PDs need to be located as soon as possible so that maintenance measures can be taken in time. Due to the structural complexity of windings, locating the PD source inside a transformer winding is not a simple task. In this paper, the effi...
متن کاملArtificial Intelligence Based Approach for Identification of Current Transformer Saturation from Faults in Power Transformers
Protection systems have vital role in network reliability in short circuit mode and proper operating for relays. Current transformer often in transient and saturation under short circuit mode causes mal-operation of relays which will have undesirable effects. Therefore, proper and quick identification of Current transformer saturation is so important. In this paper, an Artificial Neural Network...
متن کاملA Novel Flux-Based Protection Scheme for Power Transformers
Internal Turn-Turn faults (TTF) are the most common failures in power transformers, which could seriously reduce their life expectancy. Although common protection schemes such as current-baseddifferential protection are able to detect some of the internal faults, some other minor ones (such as TTFs andshort circuit near the neutral point) cannot be detected by such schemes. Likewise, these rela...
متن کاملAcoustic Detection of Partial Discharges in Insulation Oil
In this paper, we performed an insulation diagnosis technique for oil-immersed power transformers by an acoustic detection method. Electrode system such as needle to plane electrode was fabricated to simulate a defect of power transformers. In addition, the frequency spectrum of acoustic signals with partial discharge (PD) in insulating oil was analyzed. From the FFT result, the frequency spect...