Sensitivity of the loading margin to voltage collapse with respect to arbitrary parameters

نویسندگان

  • Scott Greene
  • Ian Dobson
  • Fernando L. Alvarado
چکیده

Loading margin is a fundamental measure of proximity to voltage collapse. Linear and quadratic estimates to the variation of the loading margin with respect to any system parameter or control are derived. Tests with a 118 bus system indicate that the estimates accurately predict the quantitative effect on the loading margin of altering the system loading, reactive power support, wheeling, load model parameters, line susceptance, and generator dispatch. The accuracy of the estimates over a useful range and the ease of obtaining the linear estimate suggest that this method will be of practical value in avoiding voltage collapse.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Improving Voltage Stability Margin Using Voltage Profile and Sensitivity Analysis by Neural Network

This paper presents a new approach for estimating and improving voltage stability margin from phase and magnitude profile of bus voltages using sensitivity analysis of Voltage Stability Assessment Neural Network (VSANN). Bus voltage profile contains useful information about system stability margin including the effect of load-generation, line outage and reactive power compensation so, it is ad...

متن کامل

Margin and Sensitivity Methods for Security Analysis of Electric Power Systems

Reliable operation of large scale electric power networks requires that system voltages and currents stay within design limits. Operation beyond those limits can lead to equipment failures and blackouts. Security margins measure the amount by which system loads or power transfers can change before a security violation, such as an overloaded transmission line, is encountered. This thesis shows h...

متن کامل

Optimal Load Shedding for Voltage Stability Enhancement by Genetic Algorithm

Outage of a heavily loaded transmission line or tripping of large generating unit may lead the system toward collapse. Under such circumstances, compared to other measures, load shedding procedure is an efficient method to make the power system voltage stable when many system variables are out of their normal ranges and the system is driven toward collapse. This paper introduces the concept of ...

متن کامل

The Irrelevance of Load Dynamics for the Loading Margin to Voltage Collapse and Its Sensitivities

The loading margin to a saddle-node orfold bifurcation is a useful and basic index of proximityto voltage collapse. Sensitivities of the loading margincan be used to select controls to avoid voltage collapse.This paper justifies the use of static power models to com-pute loading margins and their sensitivities. In particular,dynamic load models may be reduced to static e...

متن کامل

The irrelevance of electric power system dynamics for the loading margin to voltage collapse and its sensitivities

The loading margin to a saddle-node or fold bifurcation measures the proximity to voltage collapse blackouts of electric power transmission systems. Sensitivities of the loading margin can be used to select controls to avoid voltage collapse. We analytically justify the use of static models to compute loading margins and their sensitivities and explain how the results apply to underlying dynami...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

عنوان ژورنال:

دوره   شماره 

صفحات  -

تاریخ انتشار 1997