Moisture Migration in an Oil-Paper Insulation System in Relation to Online Partial Discharge Monitoring of Power Transformers
نویسندگان
چکیده
Most power transformers operating in a power system possess oil-paper insulation. A serious defect of this type of insulation, which is associated with long operation time, is an increase in the moisture content. Moisture introduces a number of threats to proper operation of the transformer, e.g., ignition of partial discharges (PDs). Due to the varying temperature of the insulation system during the unit’s normal operation, a dynamic change (migration of water) takes place, precipitating the oil-paper system from a state of hydrodynamic equilibrium. This causes the PDs to be variable in time, and they may intensify or extinguish. Studies on model objects have been conducted to determine the conditions (temperature, humidity, time) that will have an impact on the ignition and intensity of the observed phenomenon of PDs. The conclusions of this study will have a practical application in the evaluation of measurements conducted in the field, especially in relation to the registration of an online PD monitoring system.
منابع مشابه
Moisture Equilibrium in Transformer Paper - Oil Systems
he presence of moisture in a transformer deteriorates transformer insulation by decreasing both the electrical and mechanical strength. In general, the mechanical life of the insulation is reduced by half for each doubling in water content [l]; the rate of thermal deterioration of the paper is proportional to its water content [2]. Electrical discharges can occur in a high voltage region due to...
متن کاملPartial Discharge Monitoring in Power Transformers Using Low-Cost Piezoelectric Sensors
Power transformers are crucial in an electric power system. Failures in transformers can affect the quality and cause interruptions in the power supply. Partial discharges are a phenomenon that can cause failures in the transformers if not properly monitored. Typically, the monitoring requires high-cost corrective maintenance or even interruptions of the power system. Therefore, the development...
متن کاملDevelopment of a Moisture-in-Solid-Insulation Sensor for Power Transformers
Moisture is an important variable that must be kept under control to guarantee a safe operation of power transformers. Because of the hydrophilic character of cellulose, water mainly remains in the solid insulation, while just a few parts per million are dissolved in oil. The distribution of moisture between paper and oil is not static, but varies depending on the insulation temperature, and th...
متن کاملClassification of Acoustic Emission Based Partial Discharge in Oil Pressboard Insulation System Using Wavelet Analysis
Insulation used in transformer is mostly oil pressboard insulation. Insulation failure is one of the major causes of catastrophic failure of transformers. It is established that partial discharges (PD) cause insulation degradation and premature failure of insulation. Online monitoring of PDs can reduce the risk of catastrophic failure of transformers. There are different techniques of partial d...
متن کاملCorrelation of Dga, Uhf Pd Measurement and Vibration Data for Power Transformer Monitoring
Reliability of electrical energy networks depends on quality and availability of electrical equipment like power transformers. Local failures inside their insulation may lead to catastrophic breakdowns. To prevent destroying events power transformers are e.g. tested on partial discharge (PD) activity. As testing is just snapshot information about transformers condition, permanent online monitor...