Diagnosis of Power Transformer Faults based on Five Fuzzy Ratio Method
نویسنده
چکیده
Dissolved Gas Analysis is one of the most useful method to detect incipient faults in transformer. Amongst the conventional DGA methods, IEC three ratio method is widely used. One of the disadvantages in its present form is that a significant number of DGA results inservice fall outside the existing IEC codes and cannot be diagnosed. To overcome this limitation, additional eighteen new combinations to the existing nine are proposed in this paper. Further, Ratio codes are quantized to define the crisp boundaries of 0,1 and 2. In practice these boundaries are non crisp (Fuzzy) especially under multiple faults condition. These codes could lead to errors in diagnosis moving across the crisp boundaries from one fault to another. To overcome these limitations, Five Fuzzy ratio method for diagnosis of multiple faults is developed. The paper used 100 different cases to test the accuracy of these methods in interpreting the transformer condition. Key-words: Expert System (ES),Dissolved Gas Analysis(DGA),International Electro Commission Method (IEC), Incipient Faults, Power Transformer, Fault Diagnosis, Fuzzy Diagnostic System, Ratio Methods.
منابع مشابه
Power Auto-transformer Mechanical Faults Diagnosis Using Finite Element based FRA
Frequency response analysis (FRA) is a sensitive method established for testing the mechanical integrity of transformers. However, interpretation of FRA signature still needs expert opinions and there is no FRA interpretation code generally accepted. Various mechanical faults with different extents on power transformers are required to aid FRA interpretation. To address this challenge, in...
متن کاملFuzzy Decision on Transformer Fault Diagnosis using Dissolved Gas Analysis and IEC Ratio Codes
This paper emphasizes on the use of fuzzy approach in dealing with the incipient fault conditions of power transformer. DGA (Dissolved Gas in Oil Analysis) cannot provide better fault diagnosis results when multiple faults are involved. The boundary values specified by the ratio methods are of limited concern .Considering the limitations of convergence of the conventional neural networks in the...
متن کاملIntuitionistic Fuzzy Expert System based Fault Diagnosis using Dissolved Gas Analysis for Power Transformer
In transformer fault diagnosis, dissolved gas analysis (DGA) is been widely employed for a long period and numerous methods have been innovated to interpret its results. Still in some cases it fails to identify the corresponding faults. Due to the limitation of training data and non-linearity, the estimation of key-gas ratio in the transformer oil becomes more complicated. This paper presents I...
متن کاملFuzzy Logic Application in DGA Methods to Classify Fault Type in Power Transformer
Assessment of power transformer conditions has become increasingly important in recent years. As an asset that represents one of the largest investments in a utility’s system, detection of incipient faults in power transformers is crucial. Dissolved gas-in-oil analysis (DGA) is a successful technique to detect these potential faults and it provides wealth of diagnostic information. This project...
متن کاملDiagnosis of Transformer Faults Based on Adaptive Neuro-Fuzzy Inference System
Transformer fault diagnosis is an interesting subject for plant operators due to its criticality in power systems. There are several international standards available to interpret power transformer faults based on dissolved gas analysis. In certain cases these standards are not able to provide correct diagnosis. There are several soft computing techniques available for modelling transformer fau...
متن کامل