Harmonics detection using prony frequency analysis algorithm in transformer inrush current generation after fault clearance
نویسندگان
چکیده
The traditional infrastructure of power system industry is presently going through large amount of change that consensus over the improvement of power quality for fulfilling this requirement electronically automated devices having high sensitivity toward the disturbance in the power system signals are under the major consensus of research activities. The low power quality signal is responsible for malfunctioning of equipments that result in reduction of production and rise in the cost of production. In the modern age electronic convertors, facts and other thyristor controlled devices is combine with the new power transmission schemes. That produces harmonics current of high frequency order and brings large amount of current and voltage quality distortion. In this paper we are investigating and implementing the Prony harmonics analysis algorithm for estimation of harmonics in the voltage cycle available during saturable core transformer energizing the result are validate and compared with the short time Fourier analysis our proposed approach found to be more accurate and aliquant for non linear discrete data signals.
منابع مشابه
transformer differential protection using the fault-generated high-frequency transient components
Power transformers are the most important components of a power system, so their protection is a critical issue. This paper proposes a novel and efficient algorithm based on the high-frequency components of the differential current signal to discriminate between the magnetizing inrush currents and the internal faults. After detecting the over-current in the differential current signals, samples...
متن کاملA New Differential Protection Algorithm Based on Rising Rate Variation of Second Harmonic Current
In this paper, a new algorithm based on processing differential current harmonics is proposed for digital differential protection of power transformers. This algorithm has been developed by considering different behaviors of second harmonic components of the differential currents under fault and inrush current conditions. In the new method, a criterion function is defined in terms of the time v...
متن کاملDiscrimination between Inrush and Fault in Transformer: ANN Approach
Transformer protection is critical issue in power system as the issue lies in the accurate and rapid discrimination of magnetizing inrush current from internal fault current. Artificial neural network has been proposed and has demonstrated the capability of solving the transformer monitoring and fault detection problem using an inexpensive, reliable, and noninvasive procedure. This paper gives ...
متن کاملDiscrimination Between Inrush and Short Circuit Currents in Differential Protection of Power Transformer Based on Correlation Method Using the Wavelet Transform
(Received: October 30, 2011; Accepted: December 8, 2011) Abstract: This paper presents a novel technique for transformer differential protection to prevent incorrect operation due to inrush current. The proposed method in this paper is based on time-frequency transform known as the Wavelet transform. The discrete Wavelet transform is used for analysis the differential current signals in time an...
متن کاملProtection Scheme of Power Transformer Based on Time–Frequency Analysis and KSIR-SSVM
The aim of this paper is to extend a hybrid protection plan for Power Transformer (PT) based on MRA-KSIR-SSVM. This paper offers a new scheme for protection of power transformers to distinguish internal faults from inrush currents. Some significant characteristics of differential currents in the real PT operating circumstances are extracted. In this paper, Multi Resolution Analysis (MRA) is use...