Involvement of cost savings and voltage stability indices in optimal capacitor allocation in radial distribution networks using artificial bee colony algorithm
نویسنده
چکیده
This article applies the artificial bee colony algorithm to define and allocate static shunt capacitors along radial distribution networks. The objective function is adapted to maximise net yearly savings and to enhance the overall system static voltage stability index with weighting and magnifying factors. Load variations have been considered to optimally size the fixed and switched capacitors required. Nodes with higher loss sensitivity factors and lower voltage stability indices are initially identified for capacitor allocations. The proposed algorithm ascertains optimal sizing and placement, and takes the final decision for optimum locations among the number of buses nominated. The realised numerical results are compared with those found by other recent heuristic methods and show that the proposed method is capable of producing high-quality solutions and validated its viability and applicability. 2014 Elsevier Ltd. All rights reserved.
منابع مشابه
Multi-objective Capacitor Allocations in Distribution Networks using Artificial Bee Colony Algorithm
This article addresses an efficient heuristic-based approach to assign static shunt capacitors along radial distribution networks using the artificial bee colony algorithm. The objective function is adapted to enhance the overall system static voltage stability index and to achieve maximum net yearly savings. Load variations have been considered to optimally scope the fixed and switched capacit...
متن کاملOptimal Reconfiguration and Capacitor Allocation in Radial Distribution Systems Using the Hybrid Shuffled Frog Leaping Algorithm in the Fuzzy Framework
In distribution systems, in order to diminish power losses and keep voltage profiles within acceptable limits, network reconfiguration and capacitor placement are commonly used. In this paper, the Hybrid Shuffled Frog Leaping Algorithm (HSFLA) is used to optimize balanced and unbalanced radial distribution systems by means of a network reconfiguration and capacitor placement. High accuracy and ...
متن کاملMulti Objective Allocation of Distributed Generations and Capacitor Banks in Simultaneous
This paper has developed a novel multiobjective function for optimal sizing and sitting ofDistributed Generation (DG) units and capacitor banks in simultaneous mode to improve reliabilityand reduce energy losses. The proposed function consists of four objectives: Cost of Energy NotSupplied (CENS), System Average Interruption Duration Index (SAIDI), costs of energy loss andinvestment. A novel st...
متن کاملOptimal Capacitor Allocation in Radial Distribution Networks for Annual Costs Minimization Using Hybrid PSO and Sequential Power Loss Index Based Method
In the most recent heuristic methods, the high potential buses for capacitor placement are initially identified and ranked using loss sensitivity factors (LSFs) or power loss index (PLI). These factors or indices help to reduce the search space of the optimization procedure, but they may not always indicate the appropriate placement of capacitors. This paper proposes an efficient approach for t...
متن کاملA Hybrid Algorithm for Optimal Location and Sizing of Capacitors in the presence of Different Load Models in Distribution Network
In practical situations, distribution network loads are the mixtures of residential, industrial, and commercial types. This paper presents a hybrid optimization algorithm for the optimal placement of shunt capacitor banks in radial distribution networks in the presence of different voltage-dependent load models. The algorithm is based on the combination of Genetic Algorithm (GA) and Binary Part...
متن کامل