Pd Patterns Recognition in Xlpe Cable under Various Thermal Conditions Using Statistical Technique
نویسندگان
چکیده
Condition monitoring of partial discharge (PD) has become a preferred method in the design of HV apparatus. Power cable is one of the HV apparatus affected by PD activity. Although, the phenomenon of PD in power cables are well known, the effect of soil thermodynamics on PD is not yet well established. Thus, an experiment has been carried out to assess the effect of soil thermal resistivity on various PD parameters at different temperatures. Cable sample studied is an 11kV, single core, 240mm 2 XLPE cable. Classification is firstly carried out using the conventional method “Recognition Rate”. A proposed method, which is called “Hitting Pattern”, is then introduced to overcome the limitation of “Recognition Rate”. Classification using “Hitting Pattern” emphasises on the patterns of discharge, which is not considered by the “Recognition Rate”. These two techniques are developed with the help of 27 statistical parameters, so called “classifiers”, which are calculated using PD Analyzer Programme developed in-house. The values of classifiers of standard physical condition are used to classify PD patterns of non-standard physical conditions. The authors have also discussed about the simplified version of “Recognition Rate”, which is called “Fingerprint”, for the easier observation purposes.
منابع مشابه
تخمین عمر عایقی کابل های فشار قوی XLPE تحت تنش های حرارتی، الکتریکی و همزمان
The aging of insulating materials can be estimated by an electrical breakdown occurring in electrical components so that the relationship between lifetime, failure probability and reliability of electrical components may be studied using the life models in high voltage cables networks. In last decades with attention to higher features as electrical, thermal, mechanical characteristic, widely cr...
متن کاملClassification of Partial Discharge Measured under Different Levels of Noise Contamination
Cable joint insulation breakdown may cause a huge loss to power companies. Therefore, it is vital to diagnose the insulation quality to detect early signs of insulation failure. It is well known that there is a correlation between Partial discharge (PD) and the insulation quality. Although many works have been done on PD pattern recognition, it is usually performed in a noise free environment. ...
متن کاملInvestigation of the Ampacity of a Prefabricated Straight-Through Joint of High Voltage Cable
This paper presents a theoretical and experimental study on the ampacity of the prefabricated straight-through joint of a 110 kV high voltage cable. Thermal modelling revealed that the critical spot limiting the ampacity of this type of cable joint is located on its crosslinked polyethylene (XLPE) insulation section. The axial distribution of the thermal field in this type of cable joint was al...
متن کاملOn-line Partial Discharge Monitoring System and Data Processing Using WTST-NST Filter for High Voltage Power Cable
Defects inside insulation of HV XLPE cable accessories can lead to partial discharge (PD) activity. When PD activity happens, leakage current may flow through the grounded line. To acquire the PD current signal, one practicable and effective method is placing a high frequency current transformer (HFCT) winding the grounded line. In order to measure the insulation degradation, a partial discharg...
متن کاملOn-line Partial Discharge Monitor System of XLPE Power Cable Based on Virtual Instrument
High voltage XLPE power cable is a very important part of power system. The degree of electric-tree aging in the cable can be estimated effectually by measuring partial discharge. An on-line partial discharge monitor system of XLPE power cable was developed based on the virtual instrument designing conception. This system has the advantage of wide analog bandwidth, excellent anti-interference a...
متن کامل