analysis of fouling in hvac heat exchangers by cfd

نویسندگان

mohammad reza jafari nasr

aida balaei

چکیده

the purpose of this study is to identify parameters influence on the particle deposition within fin and tube heat exchanger of air-conditioning systems by cfd analysis. first the basic sketch of periodic geometry drawn and meshing operation including boundary conditions was performed. then the gas side properties and flow parameters were solved by ansys fluent 14.5 software. lagrangian equations used for modeling dispersed phase and effect of injecting various particle sizes evaluated by rosin-rammler model. moreover turbulence effect was investigated using discrete random walk model. consequently it is observed that deposition rate is highly affected by particles diameter in which leads to 90% deposition for particles over 30 µm in diameter.

Sign up for free to access the full text

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Analysis of Fouling in HVAC Heat Exchangers by CFD

The purpose of this study is to identify parameters influence on the particle deposition within fin and tube heat exchanger of air-conditioning systems by CFD analysis. First the basic sketch of periodic geometry drawn and meshing operation including boundary conditions was performed. Then the gas side properties and flow parameters were solved by ANSYS Fluent 14.5 software. Lagrangian equa...

متن کامل

Fouling of Heat Exchangers by Dairy Fluids – a Review

* Current address: Fonterra Co-operative Group Ltd, Private Bag 11029, Palmerston North, New Zealand Email: [email protected] ABSTRACT Fouling of heat exchangers in the dairy industry has been investigated extensively and a large number of studies are reported in literature. This review focuses on the mechanisms of milk fouling, detailing the role of protein denaturation and aggregation...

متن کامل

Fouling of Heat Exchangers in the Dairy Industry

J. Visser Th. J. M. Jeurnink NIZO, 6710 BA Ede, Netherlands N A general overview is given of the main factors in the fouling of processing equipment used for heating dairy fluids. The data collected indicate that the primary step in fouling is the adsorption of a monolayer of proteins onto the wall of the heating equipment at room temperature. Real fouling (i.e., the formation of macroscopic la...

متن کامل

Detection of Fouling in Heat Exchangers using Model Comparison

Fouling of heat exchangers is a severe problem in the industrialized world. The effects of fouling are reduced energy efficiency and increased greenhouse gas emissions. In fact, any heat transfer process has a risk of fouling on the heat transfer surface. The fouling can in some cases be cleaned physically, chemically or burned off; in other cases it may not be possible to clean the heat exchan...

متن کامل

منابع من

با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید


عنوان ژورنال:
iranian journal of chemistry and chemical engineering (ijcce)

ناشر: iranian institute of research and development in chemical industries (irdci)-acecr

ISSN 1021-9986

دوره 34

شماره 3 2015

میزبانی شده توسط پلتفرم ابری doprax.com

copyright © 2015-2023