This article introduces a new time-domain fault location algorithm for two-terminal parallel transmission lines connected to large scale wind farms. The proposed employs only half-cycle data window of synchronized current samples at both line terminals avoid inaccurate estimation phasors due the generated sub- and inter-harmonics currents by does not need any transformation method decouple double-circuit line. Moreover, it takes into consideration effect asymmetry potential couplings between six phases. equation is deduced equalizing differential components calculated instantaneous voltages point, then distance estimated directly without iterative algorithm. emulated PSCAD/EMTDC platform utilizing frequency-dependent phase model, required calculations are conducted MATLAB software. tested several resistances locations, all types, including cross-circuit faults. In addition, measurement, synchronization, parameters errors on accuracy investigated. obtained results confirm acceptable
منابع مشابه
Fault Location Method for STATCOM Connected Transmission Lines Using CCM
Determining the fault location using conventional impedance based distance relay in the presence of FACTS controllers is a challenging task in a transmission line. A new distance protection method is developed to locate the fault in a transmission line compensated with STATCOM with simple calculations. The proposed protection method considers the STATCOM injected/absorbed current to correct the...
متن کاملA Novel Fault Phase Selector for Double-Circuit Transmission Lines
A novel fault phase selector for double-circuit transmission lines is presented. The fault type is determined with the superimposed components and steady state components of fault voltage. According to the determined fault type, auxiliary criteria based on the magnitude and phase difference of fault phase current is applied to judge whether inter-line fault happens or not. If inter-line fault h...
متن کاملA Genetic Based Fault Location Algorithm for Transmission Lines
Overhead transmission lines are parts of the electric power system where fault probabilities are generally higher than that of other system components. One of the main objective of protective system is to detect faults on transmission lines as fast as possible. Another important job is to locate this fault point accurately. Therefore, it is very important to have a fast reliable methods that ca...
متن کاملOnline One-End Fault Location Algorithm for Parallel Transmission Lines
Fault location and distance protection are essential smart grid technologies ensuring reliability of the power system. This paper describes an accurate algorithm for locating faults on double-circuit transmission lines. The proposed approach is capable of identifying the faulted circuit of a parallel transmission line by checking the estimated fault location and fault resistance. Voltage and cu...
متن کاملFault Location on Compensated Transmission Lines without Current Measurement
This paper presents a novel fault location method for series compensated transmission lines. It is established based on synchronized voltages sampling and Thevenin impedance from both ends of series compensated transmission line. The method is based on the use of phasor measurement units (PMU) technology which is aimed to be independent of current measurements, fault type, fault resistance, fau...