Analysis and Control of Battery Energy Storage System Based on Hybrid Active Third-Harmonic Current Injection Converter
نویسندگان
چکیده
This paper applies the emerging hybrid active third-harmonic current injection converter (H3C) to battery energy storage system (BESS), forming a novel H3C-BESS structure. Compared with commonly used two-stage VSC-BESS, proposed has capability reduce passive components and switching losses. The operation principle of is analyzed mathematical model derived. closed-loop control strategy controller design are for different modes system, which include current/voltage injected harmonic control. In particular, damping realized through grid control, could suppress LC-filter resonance without need resistors. Simulation results show that topology its have fast dynamic response, setup time less than 4 ms. addition, total distortions currents only 2.54% 3.15%, respectively. amplitude half current, indicating circuit generates low Experimental also provided verify validity solution.
منابع مشابه
Control of Cascaded DC-DC Converter-Based Hybrid Battery Energy Storage Systems - Part I: Stability Issue
متن کامل
Control of Cascaded DC-DC Converter-Based Hybrid Battery Energy Storage Systems - Part II: Lyapunov Approach
متن کامل
Modeling and Efficient Control of Microturbine Generation System With Battery Energy Storage for Sensitive Loads
Microturbine generation system is one of the most promising and a fast growing distributed generation sources. It is used in various applications thanks to high efficiency, quick start and high reliability. Combination of the microturbine and storage system (e.g. battery bank) is desirable selection to satisfy the load requirements under all conditions and hence the battery bank can play an imp...
متن کاملAnalysis of a New Third Harmonic Injection Active Rectifier Topology Based on an NPC Three-Level Converter Cell
Active three-phase rectifier systems usually cover a wide field of applications where high total power factor (99%+) and low mains current THDi (typ. <5%) are required. Passive three-phase rectifiers on contrary are characterized as highly efficient and robust whereas their power factor is limited to 0.9...0.95 due to rather high harmonic input current components (THDi up to 48%). This paper an...
متن کاملDesign and Control of a Novel hybrid Active Power Filter based on Load Harmonic Currents Separation with the aim of DC-link voltage minimization in voltage source converter
This paper proposes a new hybrid active power filter, including voltage source converter (VSC) based active power filter and Thyristor Controllable LC Passive Filter (TCLC-HAPF) for eliminating harmonic load current components and compensating reactive power. This new structure which is based on the separation of high and low-frequency components of load current idea can reduce the drawbacks of...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
ژورنال
عنوان ژورنال: Energies
سال: 2021
ISSN: ['1996-1073']
DOI: https://doi.org/10.3390/en14113140