Decreasing Distribution Generation Effects on Grid Short Circuit Level Using Superconducting Fault Current Limiter Through Updating Relays Set-Points

نویسندگان

چکیده مقاله:

Power system protection at transmission and distribution levels based on overcurrent relays is essential based on their properties such as detection, stability, high speed, backup and error correction accuracy. Since distributed generation sources are connected to the power grid, they not only increase the short circuit level of the grid, but also disrupt the set point of main and backup relays, which will interrupt the healthy areas of the grid. In order to maintain the safety and stability of the network and to avoid increasing the power rating of the existing equipment, Superconducting Fault Current Limiter (SFCL) devices are utilized to significantly reduce the short circuit current at its primary cycles. However using of SFCLs, may lead to inadequate relay performance and lack of short circuit current detection. In order to solve the above problems, this paper presents a SFCL model with resistive structure and coupling inductance, while increasing the fault impedance path and reducing short circuit current, optimally. Then shielding synchronization between main relays and their near and far back-ups are achieved. Finally proposed objective function is minimized using the improved particle swarm optimization algorithm and three case studies will be performed. The simulation results represent the superiority of the proposed method in resolving the error and eliminating disturbance between the relays at the shortest possible time.

برای دانلود باید عضویت طلایی داشته باشید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

The Impact of Superconducting Fault Current Limiter Locations on Voltage Sag in Power Distribution System

In this paper, the impacts of installing superconducting fault current limiter (SFCL)in radial and loop power distribution system are evaluated to improve voltage sag in both cases of with and without distributed generations (DG). Among various SFCLs, the hybrid type with a superconducting element in parallel with a current limiting reactor (CLR) is selected. This is more effective than resisto...

متن کامل

the impact of superconducting fault current limiter locations on voltage sag in power distribution system

in this paper, the impacts of installing superconducting fault current limiter (sfcl)in radial and loop power distribution system are evaluated to improve voltage sag in both cases of with and without distributed generations (dg). among various sfcls, the hybrid type with a superconducting element in parallel with a current limiting reactor (clr) is selected. this is more effective than resisto...

متن کامل

Influence of Fault Current Limiter in Voltage Drop and TRV Considering Wind Farm

Influence of distributed generation systems in the distribution systems can increase the level of short-circuit current. The effectiveness of distributed generation systems is affected by the size, location, type of distributed generation systems technology, and the methods of connecting to distribution systems. Wind turbine system is the examples of distributed generation source. Not only does...

متن کامل

Improvement of Low Voltage Ride – through Capability of Distributed Generation in a Microgrid Using Superconducting Fault Current Limiter

Although the introduction of distributed generation (DG) in a distribution system improves the power quality of power system, it increases the fault current level reducing voltage at point of common-coupling (PCC). Hence, there is a need of improving fault ride-through (FRT) capability to avoid sudden tripping of DG units from the utility grid during voltage sag in a faulty condition. In this p...

متن کامل

Mitigation of Distributed Generation Impact on Protective Devices in a Distribution Network by Superconducting Fault Current Limiter

Protection of radial distribution networks is widely based on coordinated inverse time overcurrent relays (OCRs) ensuring both effectiveness and selectivity. However, the integration of distributed generation (DG) into an existing distribution network not only inevitably increases fault current levels to levels that may exceed the OCR ratings, but it may also disturb the original overcurrent re...

متن کامل

Finite element modeling of a superconducting fault current limiter

This paper summarizes the work done to show finite element modeling results on a high temperature superconductor fault current limiter (FCL). The paper also gives the small mock-up design of the matrix FCL and its finite element model (FEM). It also discusses the limitations of the FEM and explains how the results from the FEM compare with the experimental data derived for the configuration. A ...

متن کامل

منابع من

با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

ذخیره در منابع من قبلا به منابع من ذحیره شده

{@ msg_add @}


عنوان ژورنال

دوره 9  شماره 3

صفحات  28- 40

تاریخ انتشار 2020-09

با دنبال کردن یک ژورنال هنگامی که شماره جدید این ژورنال منتشر می شود به شما از طریق ایمیل اطلاع داده می شود.

کلمات کلیدی

کلمات کلیدی برای این مقاله ارائه نشده است

میزبانی شده توسط پلتفرم ابری doprax.com

copyright © 2015-2023