Impact of Series Compensation Insertion in Double HV Transmission Line on the Settings of Distance Protection
نویسندگان
چکیده
This paper presents a study of the performance of distance protection relays when series compensation (SC) is inserted on double circuit transmission line high voltage (HV) 400 kV in Algeria (Group Sonelgaz). The relays setting for distance protection is considered as a great challenge to power system protection engineers. Special considerations on the transmission line impedance measurement are necessary in the application of distance protection. The studies also include different challenges which the protection engineer may face such as current and voltage inversion, non-linearity of the line impedance. A detailed modeling of SC is proposed and integrated in transmission system for five case studies in different point locations on transmission line. The proposed results dealing with distance relays protection setting are performed in MATLAB software environment, for different cases. Index Terms Distance protection, Double transmission line, High voltage, Fault, Relay, Series compensation. —————————— ——————————
منابع مشابه
A Comparative Study of GCSC and TCSC Effects on MHO Distance Relay Setting in Algerian Transmission Line
This paper presents a comparative study of the performance of distance relays for transmission line high voltage (HV) 400 kV in Eastern Algerian transmission networks at Group Sonelgaz compensated by two different series Flexible AC Transmission System (FACTS) i.e. GTO Controlled Series Capacitor (GCSC) and Thyristor Controlled Series Capacitor (TCSC) connected at midpoint of an electrical tran...
متن کاملReliable and Economical Scheme to Improve Protection and Stability of Heavily Loaded Double Circuit Transmission Lines Using Series Compensation
Tripping of one circuit of a heavily loaded doublecircuit transmission line may lead to tripping of the healthy circuit due to an out-of-step condition. Out of step is resulted by overloading of the healthy circuit. In this paper, a reliable and economical scheme of using series capacitors is proposed to avoid tripping of healthy circuit. Series Capacitors improve the power transfer capability ...
متن کاملMHO Distance Relay of Transmission Line High Voltage using Series Compensation in Algerian Networks
This paper deal with an analytical and simulation of the application of distance relay for the protection of line transmission high voltage 220 kV employing series capacitors compensating devices. A detailed modelling of series compensated (SC) is proposed and integrated in transmission system. The studies also include different challenges which the protection engineer may face such as current ...
متن کاملApplication MPSO Techniques for Setting Zones on Distance Protection in Presence Thyristor Controlled Series Capacitor
This paper presents the application of the Modified Particle Swarm Optimization (MPSO) technique for optimal settings zones for distance relay protect 400 kV single transmission line of Eastern Algerian transmission networks at Algerian Company of Electrical and Gas (Group Sonelgaz) compensated by Thyristor Controlled Series Capacitor (TCSC) connected at midpoint for minimized active and reacti...
متن کاملEffects of CT and VT Connection Point on Distance Protection of Transmission Lines with FACTS Devices
This paper presents the effects of instrument transformers connection points on the measured impedance by distance relays in the presence of Flexible Alternating Current Transmission System (FACTS) devices with series connected branch. Distance relay tripping characteristic itself depends on the power system structural conditions, pre-fault operational conditions, and especially the ground ...
متن کامل