DC Flashover Performance of Ice-Covered Composite Insulators with Parallel Air Gaps
نویسندگان
چکیده
DC flashover performance of ice-covered composite insulators with a parallel air gap (CI/PAG) is an important technical consideration when such insulators are used to isolate ground wires for the purpose of DC ice-melting. Tests on tension and suspension types of CI/PAG were thus carried out in the artificial climate chamber to investigate their DC icing flashover performance. The influences of parallel air gap, ice thickness, pollution severity and air pressure on DC negative 50% flashover voltage (U50%) of CI/PAG were investigated. Test results show that the parallel air gap affected both the discharge path and U50%. With increasing ice thickness, U50% declined by up to 52%; this effect was more evident when the breakdown occurred in the air gap. The pollution severity affected U50% only when the flashover happened along insulator surface. With a decrease of atmospheric pressure, U50% decreased. U50% and the ratio of air pressure were in a power function relationship with a positive characteristic exponent which was relevant to the discharge path.
منابع مشابه
Ion Migration in the Process of Water Freezing under Alternating Electric Field and Its Impact on Insulator Flashover
Ice flashover threatens the security and reliability of power transmission. However, the ice flashover mechanism of insulators remains poorly understood. This study analyses water droplet freezing and ion distribution in ice layer under alternating electric field. It also investigates ion migration during icing process of insulator string under alternating electric field and its effects on insu...
متن کاملPredicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations
Perhaps no single area of insulator behavior has fascinated researchers more so than predicting flashover under contaminated conditions. For traditional porcelain and glass insulators, there is a large body of literature published that includes both theoretical models and experimental tests to simulate this interesting and practically important aspect of insulator performance. Yet there still s...
متن کاملModel for Predicting DC Flashover Voltage of Pre-Contaminated and Ice-Covered Long Insulator Strings
In the current study, a multi-arc predicting model for DC critical flashover voltage of iced and pre-contaminated long insulator strings under low atmospheric pressure is developed. The model is composed of a series of different polarity surface arcs, icicle-icicle air gap arcs, and residual layer resistance. The calculation method of the residual resistance of the ice layer under DC multi-arc ...
متن کاملDesignation of an Indicator for flashover prediction of porcelain and glass insulators based on experimental tests.
Flashover of polluted insulators in contaminated areas is one of the most important factors influencing the operation of transmission and distribution lines and finally line outages. Therefore, it is essential to prevent and detect flashover in the insulators. Hence, utilizing the insulator status monitoring systems and predicting their functions have absorbed a lot of attention over the recent...
متن کاملAssessing Partial Discharge on Composite Insulators Under Desert Pollution Conditions
Transmission lines located in the Sinai desert are subjected to desert climate, one of whose features, especially in the spring, is sand storms. Line insulators are thus exposed to sand contamination, which may produce streamer discharges in the air surrounding insulator surface. Such discharges may lead to flashover. This paper examines the electric field and potential distributions on sand-po...