Experimental Assessment of Metal Foam and Louvered Fins as Air-side Heat Transfer Enhancement for Miniaturized Condensers
نویسندگان
چکیده
An experimental investigation was conducted to evaluate and compare the thermal-hydraulic performances of crossflow microchannel condensers using louvered fins and metal foams as extended surfaces. Three copper foam surfaces with pore densities of 10 and 20 PPI and porosities of 89.3% and 94.7% were compared with three aluminum louvered fins with lengths of 27 and 32 mm (in the flow direction) and heights of 5 and 7.5 mm. The experiments were carried out in a closed loop wind-tunnel calorimeter equipped with a R-600a refrigeration loop. A condensing temperature of 45°C was used in all tests, with face velocities ranging from 2.1 to 7.7 m/s. A comparison based on the air-side thermal conductance and pumping power per unit volume showed that the louvered fin surfaces performed better than the metal foams for all conditions investigated.
منابع مشابه
Experimental and simulation study on the air side thermal hydraulic performance of automotive heat exchangers
Flat tube heat exchangers with louvered fins were applied in order to meet the performance requirements and compactness in automotive air conditioning systems. Experimental and simulation study focusing on the air side thermal hydraulic performance of automotive heat exchangers were performed in this article. Test results showed that the heat capacity of a condenser with 5.4 mm height louvered ...
متن کاملMetal Foam and Finned Metal Foam Heat Sinks for Electronics Cooling in Buoyancy-Induced Convection
In this paper, we present our recent experimental results on buoyancy-induced convection in aluminum metal foams of different pore densities [corresponding to 5, 10, 20, and 40 pores per in. (PPI)] and porosities (0.89–0.96). The results show that compared to a heated surface, the heat transfer coefficients in these heat sinks are five to six times higher. However, when compared to commercially...
متن کاملAir-side Particulate Fouling of Microchannel Heat Exchangers: Experimental Comparison of Air-Side Pressure Drop and Heat Transfer with Plate-Fin Heat Exchanger
In this study, the air-side pressure drop and heat transfer performance of plate-fin and microchannel coils were tested under clean and fouled conditions. The heat exchangers were tested with two different types of dust, ASHRAE dust and Arizona Road Test Dust. The ASHRAE dust was found to have a very significant impact on the pressure drop of the microchannel heat exchanger, increasing the air-...
متن کاملExperimental Comparison of the Impact of Air-Side Particulate Fouling on the Thermo-Hydraulic Performance of Microchannel and Plate-Fin Heat Exchangers
In this study, the air-side pressure drop and heat transfer performance of plate-fin and microchannel coils were tested under clean and fouled conditions. The heat exchangers were tested with two different types of dust, ASHRAE Standard Dust and Arizona Road Test Dust. The ASHRAE dust was found to have a very significant impact on the pressure drop of the microchannel heat exchanger, increasing...
متن کاملThe Solar Air Channels: Comparative Analysis, Introduction of Arc-shaped Fins to Improve the Thermal Transfer
The problem under investigation contains a computational simulation of a specific heat exchanger with complex geometry fins. The problem solved is potentially interesting for researchers and engineers working on solar collectors and aerospace industry. It is known that heat transfer enhancement can be achieved by creating longitudinal vortices in the flow. These vortices can be generated by arc...
متن کامل