New mitigation methods for transient overvoltages in gas insulated substations
نویسندگان
چکیده
During switching of disconnectors (DS) in GIS a varying number of pre-strikes and re-strikes occur. Due to the very short duration of the voltage collapse, traveling surges are generated in the busbar duct. These very fast transient overvoltages (VFTO) can become the limiting dielectric stress which defines the dimensions at UHV voltage levels. The decision shall be based on the maximum VFTO peak value that occurs with reference to the rated lightning impulse withstand voltage (LIWV) of the equipment. If the maximum VFTO is higher than the LIWV, it is necessary to consider the VFTO level as dimensioning criteria or to suppress VFTO by suitable measures. The main challenges are the reduction in VFTO amplitudes and finally the reduction of the effects of VFTO on the equipment. For the different sources of VFTO and for the different equipment different mitigation methods are known. The damping of VFTO by integration of a damping resistor is a well proven technology. The way to overcome the drawback of such unwieldy designs is to use other internal damping measures. Several methods have been proposed and examined in the past, such as ferrite material or high frequency (RF) resonators. The VFTO damping solution utilizing ferrite rings has been analysed and tested and will be described here. The measurements show that a damping effect can be achieved, but with an important drawback: the magnetic material goes easily into saturation, which complicates the design and reduces its general applicability and robustness. A new approach for damping is to implement compact electromagnetic high-frequency resonators with low quality factor specially designed to cover a wider frequency range. The novelty of this idea is not only to design the resonators but also to dissipate the VFTO energy. The VFTO damping effect of the developed RF resonator tuned to the dominant harmonic component was confirmed by experiments. Rings of a nanocrystalline alloy placed around the GIS conductor were also investigated. Depending on number, material and size of the rings a good mitigation could be achieved.
منابع مشابه
Mitigation of Transient Overvoltages Generated Due to Switching Operations and Lightning in Gas-insulated Substation (GIS) Without Extra Limiter
Gas-insulated substations (GIS) have different specifications in proportion to air-insulated substations. Transformer failures related to lightning and switching are often reported in the gas insulated substation (GIS). This problem is the voltage magnifications due to reflections of switching and lightning surges at various junctions within the GIS. thereby overvoltages in GIS are more importa...
متن کاملAnalysis of effective factors on transient ground potential rise in gas insulated substations
This study presents the manner in which transient modeling concepts, which are fully analyzed in the referred standards, are implemented, for the purpose of evaluating the Transient Ground Potential Rise (TGPR). This is a phenomenon of 10–100kV voltages with up to 10μs duration on the grounded enclosure of Gas Insulated Substations (GIS), which may cause concern for personnel safety and problem...
متن کاملAnalysis of effective factors on transient ground potential rise in gas insulated substations
This study presents the manner in which transient modeling concepts, which are fully analyzed in the referred standards, are implemented, for the purpose of evaluating the Transient Ground Potential Rise (TGPR). This is a phenomenon of 10–100kV voltages with up to 10µs duration on the grounded enclosure of Gas Insulated Substations (GIS), which may cause concern for personnel safety and pro...
متن کاملEffect of Very Fast Transient over voltages at high frequency in a Gas Insulated Substation during switching operations
Due to the opening or closing of circuit breakers and disconnect switches in Gas Insulated Substations (GIS), especially in the pumped storage power stations, Very Fast Transient Over-voltages (VFTO) are generated. This paper describes the 500 kV and 750 kV GIS. The variations of VFTO magnitudes at different points in 500 kV and 750 kV GIS during different switching operations have been calcula...
متن کاملNanocrystalline to Suppress VFTO and VFTC for 245kV Gas Insulated Substations
Switching of disconnectors (DS) and various faults in Gas Insulated Substation (GIS) causes number of pre-strikes and re-strikes happens. The short duration voltage collapse, traveling surges in busbar causes Very Fast Transient Over voltages (VFTO) and Very fast Transient Currents (VFTC) in the GIS substation. The main challenge is to reduce VFTO and VFTC amplitudes. Several methods have been ...