Experimental investigation was done to find the role of capillary tube length and amount of refrigerant charge on the overall heat transfer coefficient in condenser and evaporator and actual COP of a simple vapour compression refrigeration system. It was concluded that increasing of the refrigerant charge in the system largely enhances the overall heat transfer coefficient in the evaporator by increasing the part of space occupied by liquid refrigerant in the evaporator. Capillary tube length is important as it decides the evaporator temperature and pressure directly but also affects the tendency of refilling of evaporator with liquid refrigerant after initial start up and alters the amount of optimum charge in the system. A simple refrigeration system should be designed with minimum possible length of capillary tube to satisfy the refrigeration conditions and maximum amount of refrigerant charged in the system limited by unwanted condition of refrigerant liquid entering the compressor.
منابع مشابه
Thermal analysis of vapour compression refrigeration system with R152a and its blends R429A, R430A, R431A and R435A
This paper presents the analysis results of R429A, R430A, R431A and R435A as drop in substitute for R152a at various evaporating temperature with condenser temperature 30°C, 40°C and 50°C. A theoretical study of thermodynamic properties such as pressure, density, and specific volume, latent heat of vaporization compression index, and critical values are done. The theoretical performance of vapo...
متن کاملOptimal Synthesis of a Cascade Refrigeration System of LNG Through MINLP Model for Pure Refrigerant Cycles
 liquefied natural gas (LNG) is the most economical way of transporting natural gas (NG) over long distances. Liquefaction of NG by using vapor compression refrigeration system requires high operating and capital cost. Due to lack of systematic design methods for multistage refrigeration cycles, the conventional approaches of determining optimal cycle configuration are mostly based on trial-an...
متن کاملExperimental Study on Al 2 O 3 - R 134 a Nano Refrigerant in Refrigeration System
In this paper, an experimental work was investigated on nanorefrigerant .Nano Al2O3-PAG oil was used as nano-refrigerant in R134a vapour compression refrigeration system . An experimental setup was designed and fabricated in the lab. The system performance was investigated using energy consumption test and freeze capacity test. The results indicate that Al2O3 nano refrigerant works normally and...
متن کاملExperimental investigation on the effect of phase change materils (PCM) in solar compression refrigeration cycle efficiency
Saving energy is one of the most important challenges of todaychr('39')s world. Reducing electrical energy consumption in compressed air systems is one of the essential requirements for designing these systems. When using domestic air conditioners (dual air conditioners) in very hot areas (Khuzestan) their performance decreases and electric current consumption increases. Therefore, the use of n...
متن کاملMethods for Improving Exergetic Efficiency of Multi-evaporators Single Compressor and Single Expansion Valve in Vapour Compression Refrigeration Systems Using Thirteen Ecofriendly Refrigerants for Reducing Global Warming and Ozone Depletion
The methods for improving second law efficiency have been considered in this paper by using liquid vapour heat exchanger is investigated in this paper. Detailed energy and exergy analysis of multi-evaporators at different temperatures with single compressor and single expansion valve using liquid vapour heat exchanger vapour compression refrigeration systems have been done in terms of performan...
متن کامل