Compensation of nonlinearities in a current transformer for the reconstruction of the primary current
نویسندگان
چکیده
The measurement of the current in industrial electrical devices is often carried out by current transformers. The reliability of these devices is compromised when the measured current is higher than the nominal value, due to the saturation and hysteresis effects of the magnetic core. In this paper, a nonlinear model of the current transformer is identified by means of a separable least squares technique. This model is successfully employed for the estimation of the primary current starting from experimental measurements of the distorted secondary current. In this way, a fair estimate of the primary current is obtained even when its maximum intensity reaches up to 60 times (or more) its nominal value. Some sensible experimental trials are reported in order to demonstrate the effectiveness of the technique developed.
منابع مشابه
Dynamic Compensation of Electrical Power Systems Using Multilevel Voltage Source Inverter
A New Static Var Generator (SVG), using cascaded full-bridge inverters (FBI) with binary output levels and the parallel connections of two cascaded inverters by means of current sharing reactor in each phases is introduced. The new M-level inverter, where M is 2n+2 - 3, consists of only 2n single-phase full bridges for each phases. The proposed technique not only increases the current capacity ...
متن کاملMitigation Transformer Inrush Current Using Modified Transient Current Limiter
This study presents a modified transient current limiter (MTCL) for mitigation the inrush current of transformers. The MTCL is based on conventional transient current limiter (TCL), which, its configuration is modified to overcome the TCL drawbacks of operation. The proposed MTCL offers lower power losses and voltage/current THD during normal operation mode. It needs only one limiting reactor i...
متن کاملComparative Power Quality Analysis of Different DSTATCOM Topologies
This paper presents the three topologies of three-phase four-wire DSTATCOM for reduction of harmonics, reactive power compensation, increasing power factor, which occur due to a nonlinear load, environment problem and polluted grid. The performances of the above topologies have been compared for the magnitude of source current, power factor improvement, DC-link voltage regulation, and total har...
متن کاملArtificial Intelligence Based Approach for Identification of Current Transformer Saturation from Faults in Power Transformers
Protection systems have vital role in network reliability in short circuit mode and proper operating for relays. Current transformer often in transient and saturation under short circuit mode causes mal-operation of relays which will have undesirable effects. Therefore, proper and quick identification of Current transformer saturation is so important. In this paper, an Artificial Neural Network...
متن کاملDetermination of a new model to study ultra-saturation phenomenon during the loaded power transformer energization and its effect on differential protection
One of transient phenomenon that causes the mal-operation of the power transformer differential protection during the energization of a loaded power transformer is the ultra-saturation phenomenon. In this paper, a new model for investigating the ultra-saturation phenomenon during the energization of a loaded power transformer is presented and its effect on the differential protection of the pow...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید
ثبت ناماگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید
ورودعنوان ژورنال:
- IEEE Trans. Contr. Sys. Techn.
دوره 9 شماره
صفحات -
تاریخ انتشار 2001