Distance Protection of Cross-Bonded Transmission Cable-Systems
نویسندگان
چکیده
In this paper the problems of protecting a cross-bonded cable system using distance protection are analysed. The combination of the desire to expand the high voltage transmission grid and the public's opinion towards new installations of overhead lines (OHL), more and more transmission cable systems are being laid around the world. Differential protection is often used for the main protection of cables. As a backup protection, distance protection is very often the preferred choice. Therefore, the behaviour of distance protection when applied to cross-bonded cablesystems is very interesting. The basic assumption of a distance relay is that the measured fault impedance is linearly dependent on the distance to fault. For this to be true, the system must be fully symmetrical and only having single-ended infeed. This is not always the case for OHL-systems and never the case for a cross-bonded cable system. The fault current returning from the fault location to the source on a cross-bonded cable system can flow in all three screens and ground. This makes the system nonsymmetrical and the zero-sequence compensation factor (kfactor) will not be able to describe the fault loop consistently for single phase faults any longer as the measured impedance becomes both non-linear and non-continuous with regard to the distance to fault.
منابع مشابه
Calculating Intermediate Faults in Underground Cables
Short-circuit calculations are extremely important in the application and setting of protective relays and the analysis of power system operations. This paper illustrates the calculation of fault currents and voltages during intermediate faults in underground cables, taking into consideration the cable sheath bonding and grounding method. The compensated ground loop impedance for faults along t...
متن کاملConsidering Pilot Protection in the Optimal Coordination of Distance and Directional Overcurrent Relays
The aim of the relay coordination is that protection systems detect and isolate the faulted part as fast and selective as possible. On the other hand, in order to reduce the fault clearing time, distance protection relays are usually equipped with pilot protection schemes. Such schemes can be considered in the distance and directional overcurrent relays (D&DOCRs) coordination to achieve faster ...
متن کاملPower Cable Protection in Transmission System
Power cable is widely used in Extra High Voltage (EHV), High Voltage (HV) transmission, Medium Voltage (MV) sub-transmission, and MV / Low Voltage (LV) distribution applications. Basically, the protection principles used for cable are similar with the ones for overhead transmission line. However, the inherent characteristics of cables make its fault behavior more complicate than that of transmi...
متن کاملEffects of CT and VT Connection Point on Distance Protection of Transmission Lines with FACTS Devices
This paper presents the effects of instrument transformers connection points on the measured impedance by distance relays in the presence of Flexible Alternating Current Transmission System (FACTS) devices with series connected branch. Distance relay tripping characteristic itself depends on the power system structural conditions, pre-fault operational conditions, and especially the ground ...
متن کاملHFC/CATV Transmission Systems (Invited Paper)
During the past decade, cable television (CATV) systems have evolved from one-way broadcast of analog video transmission to two-way hybrid fiber/coaxial (HFC) networks delivering both analog and broadband services. The broadband services include high speed internet access, cable telephony, video-on-demand, and digital video. In this talk, we describe HFC transmission systems including the infra...
متن کامل