An Efficient Method to Reduce the Peak Transient Grounding Resistance Value of a Grounding System
نویسندگان
چکیده
In this paper, an efficient method is proposed to reduce the peak transient grounding resistance (P-TGR) of a grounding system. By surrounding the lifting line with a material volume, the P-TGR of the grounding system is greatly reduced. The effect of the surrounding volume conductivity and relative permittivity on the P-TGR is also tested. Second, the rectangular surrounding material volume is shielded with a metallic pipe to reduce the P-TGR further. Third, the shielding metallic pipe is connected to the grounding electrode with thin wire, and the effect of the number of the wires on the P-TGR is also analyzed. It is demonstrated that the P-TGR of the grounding system has been reduced significantly.
منابع مشابه
Back-flashover Investigation of HV Transmission Lines Using Transient Modeling of the Grounding Systems
The article presents the transients analysis of the substation grounding systems and transmission line tower footing resistances which can affect to the back-flashover (BF) or overvoltage across insulator chain in an HV power systems by using EMTP-RV software. The related transient modeling of the grounding systems is based on a transmission line (TL) model with considering the soil ionization....
متن کاملارائۀ یک روش نوین بهمنظور مدلسازی جامع سیستم زمین دکلهای فشار قوی و برج توربینهای بادی با استفاده از روش برازش برداری
In the past, grounding systems usually were modeled by an individual Resistor. This estimation is useful only at low frequencies, while in high frequencies, the inductance of the grounding system plays the main role to identify the phase and amplitude of that. In recent years, as wind farms grow rapidly throughout the world, the grounding system and ground impedance of wind turbine towers under...
متن کاملبررسی جامع اضافهولتاژهای صاعقه در مزارع بادی با پیکربندیهای متفاوت به همراه تاثیر سیستم زمین
This paper is treated with major risks applied by lightning strikes to wind farms. The risks illustrated in this research include overvoltage caused by direct and indirect effects of lightning strikes on any components of wind farm. As demands for electrical energy throughout our world is increased more and more nowadays, wind power plants are extended in every possible locations correspondingl...
متن کاملImpact of Ocean-Land Mixed Propagation Path on Equivalent Circuit of Grounding Rods
In this paper, the effect of ocean-land mixed propagation path on the lightning performance of grounding rods is investigated. This effect is focused on two problems. The first is extracting exact equivalent circuit of grounding rods in the presence of oceans. The equivalent circuit can be used in transient analysis of power systems in the neighboring oceans. In the second one, this effect on t...
متن کاملطراحی بهینه، ایمن و اقتصادی سیستم زمین پستهای فشارقوی
Due to both safety and economic issues, exhaustive and optimal design of the grounding system of high voltage substations is one of the most important, expensive, sensitive, and complicated problems of the high voltage substations. In this paper, a novel designing method is proposed which consist of seven fundamental steps. The method is based on the ANSI/IEEE Std. 80-2000 standard. Most of the...