Research of PMU Optimal Placement in Power Systems
نویسندگان
چکیده
The analysis of power system observability and the rules of PMU placement are concisely presented. Several algorithms of PMU placement as well as their differences and relations are discussed in details: a graph-theoretic procedure based on Depth First Search can find the optimal placement the most quickly; Simulated Annealing Method can help the algorithm converge to global optimum. Base on these two algorithms, an improved algorithm: Minimum Spanning Tree Method is proposed. It keeps good balance of quality and efficiency of the optimal placement, and improves the multiformity of the results by improving the optimization rule of Depth First Search Method. Key-Words: Phasor Measurement Unit (PMU); Observability; Depth First Search; Simulated Annealing Method; Minimum Spanning Tree; Optimal PMU Placement (OPP)
منابع مشابه
PMU Placement Methods in Power Systems based on Evolutionary Algorithms and GPS Receiver
In this paper, optimal placement of Phasor Measurement Unit (PMU) using Global Positioning System (GPS) is discussed. Ant Colony Optimization (ACO), Simulated Annealing (SA), Particle Swarm Optimization (PSO) and Genetic Algorithm (GA) are used for this problem. Pheromone evaporation coefficient and the probability of moving from state x to state y by ant are introduced into the ACO. The modifi...
متن کاملOptimal PMU Placement Considering with HVDC Links and Their Voltage Stability Requirements
In wide area measurement systems, PMUs are the main component measuring real time synchronized data from different buses. Installation of PMUs at all buses is a primary way to provide full observability of the power network. However, it is not practical in real networks due to the relatively expensive cost of PMUs and other technical limitations. Optimal PMU Placement (OPP) is an optimization p...
متن کاملObservability-Enhanced PMU Placement Considering Conventional Measurements and Contingencies
Phasor Measurement Units (PMUs) are in growing attention in recent power systems because of their paramount abilities in state estimation. PMUs are placed in existing power systems where there are already installed conventional measurements, which can be helpful if they are considered in PMU optimal placement. In this paper, a method is proposed for optimal placement of PMUs incorporating conve...
متن کاملPresenting a New Method Based on Branch Placement for Optimal Placement of Phasor Measurement Units
In this paper, a new method based on branch placement for the optimal positioning of Phasor Measurement Units (PMUs) in power systems is proposed. In this method, the PMUs are in type of single-channel and are installed at the beginning of the branches. Therefore, they are able to measure the bus voltages. Also, the installation of the PMUs on the branches increases the security of observabilit...
متن کاملOptimal Placement of Phasor Measurement Units to Maintain CompleteObservability Considering Maximum Reliability by Non-dominated Sorting Genetic Algorithm-II (NSGA-II)
Ever-increasing energy demand has led to geographic expansion of transmission lines and their complexity. In addition, higher reliability is expected in the transmission systemsdue to their vital role in power systems. It is very difficult to realize this goal by conventional monitoring and control methods. Thus, phasor measurement units (PMUs) are used to measure system parameters. Although in...
متن کاملOptimal Placement of Phasor Measurement Units in Khorasan Network Using a Hybrid Intelligent Technique
In this paper, an efficient and comprehensive hybrid intelligent technique for the optimal placement of phasor measurement units (PMUs) is proposed to minimize the number of PMU installation subjected to full network observability. Three main purposes of PMUs output synchronous measurements are monitoring, control, and protection of power system. We have combined Binary Imperialistic Competitio...