A New Method to Identify Fault Current and Inrush Current on Transformer by Jiles–atherton Model
نویسندگان
چکیده
This paper proposes a new method to detect transformer inside incipient fault current using transformer internal parameters to determine the inside structure of transformer at good condition or bad. A transformer model was established by Jiles– Atherton theory using measured voltage and current and the initial parameters which were found using Genetic Algorithm (GA). Then, transformer internal parameters k and c can be estimated using Simplex method to easily differentiate inrush currents and incipient fault currents.
منابع مشابه
A New Restricted Earth Fault Relay Based on Artificial Intelligence
The restricted earth fault (REF) relay is a type of differential protection which is used for detection of internal ground faults of power transformers. But, during external faults and transformer energization conditions, the probability of current transformer (CT) saturation increases. Thus, the spurious differential current due to CT saturation, can lead to REF relay maloperation. In this pap...
متن کاملAutomatic J–A Model Parameter Tuning Algorithm for High Accuracy Inrush Current Simulation
Inrush current simulation plays an important role in many tasks of the power system, such as power transformer protection. However, the accuracy of the inrush current simulation can hardly be ensured. In this paper, a Jiles–Atherton (J–A) theory based model is proposed to simulate the inrush current of power transformers. The characteristics of the inrush current curve are analyzed and results ...
متن کاملProtection Scheme of Power Transformer Based on Time–Frequency Analysis and KSIR-SSVM
The aim of this paper is to extend a hybrid protection plan for Power Transformer (PT) based on MRA-KSIR-SSVM. This paper offers a new scheme for protection of power transformers to distinguish internal faults from inrush currents. Some significant characteristics of differential currents in the real PT operating circumstances are extracted. In this paper, Multi Resolution Analysis (MRA) is use...
متن کاملDiscrimination of Inrush from Fault Currents in Power Transformers Based on Equivalent Instantaneous Inductance Technique Coupled with Finite Element Method
The phenomenon of magnetizing inrush is a transient condition, which occurs primarily when a transformer is energized. The magnitude of inrush current may be as high as ten times or more times of transformer rated current that causes malfunction of protection system. So, for safe running of a transformer, it is necessary to distinguish inrush current from fault currents. In this paper, an equiv...
متن کاملDesigning of a New Transformer Ground Differential Relay Based on Probabilistic Neural Network
Low- impedance transformer ground differential relay is a part of power transformer protection system that is employed for detecting the internal earth faults. This is a fast and sensitive relay, but during some external faults and inrush current conditions, may be exposed to maloperation due to current transformer (CT) saturation. In this paper, a new intelligent transformer ground differentia...
متن کامل