A Hybrid Anti-islanding Method for Inverter-Based Distributed Generation
نویسندگان
چکیده
Nowadays, high penetration of Distributed Generations (DG)s in power systems caused some protection issues. One of these issues is unintentional islanding. As regards IEEE 1547 standard, this situation must be recognized immediately, and DG must be separated from the load in less than 2 seconds. In this paper, to detection of islanding in an inverter-based distributed generation, a new hybrid method with high performance is proposed. In the proposed method, a primary detection of islanding is conducted by measuring the voltage harmonic distortion at the Point of Common Coupling (PCC), as well as comparing the variations to a specified threshold level. After this primary detection, a temporary reactive current signal is injected to the PCC by the inverter of DG, and its terminal voltage and frequency are measured. In the case of deviation of voltage or frequency from permissible range, definitive detection of islanding is determined. Simulation results indicate the efficiency and accuracy of the proposed detection method in different circumstances, especially for loads with the different quality factors.
منابع مشابه
Over/Undervoltage and Undervoltage Shift of Hybrid Islanding Detection Method of Distributed Generation
The mainly used local islanding detection methods may be classified as active and passive methods. Passive methods do not perturb the system but they have larger nondetection zones, whereas active methods have smaller nondetection zones but they perturb the system. In this paper, a new hybrid method is proposed to solve this problem. An over/undervoltage (passive method) has been used to initia...
متن کاملIslanding Detection Method for Inverter Based Distributed Generation Based on Combined Changes of Rocoap and Rocorp
Nowadays, renewable energies are very crucial and have a special place in the world. Renewable-energy resources are utilized by most of the Distributed Generations (DG) in the grid interconnected power system. Due to the advantages of renewable energy resources like clean nature, pollution free, cost free, the use of they are increasing in daily life. The major problems due to such distributed ...
متن کاملارایه روشی ترکیبی نوین بر اساس نسل دوم تبدیل موجک و روش جابجایی فرکانس ساندیا برای تشخیص کارکرد جزیره ای در تولیدات پراکنده مبتنی بر اینورتر
This paper is introducing a new controlling scheme with second generation wavelet transform and sandia frequency shift (SFS) for islanding detection of inverter-based distributed generation. This new hybrid method combines two active and passive methods through two performance zones. The new hybrid method calculates energy entropy of wavelet coefficients in its passive zone and if it increases ...
متن کاملInverter based distributed generator islanding detection method using U/O voltage relay
Islanded operation of distributed generators is a problem that can take place when they are connected to a distribution system. In this paper an islanding detection method is presented for inverter based distributed generation (DG) using under/over voltage relay. The method is an adaptive one and is based on the change of DG active power reference (Pref) in inverter control interface. The activ...
متن کاملA Proposed Hybrid Method For Islanding Detection
In this paper Islanding detection methods for distributed resources are reviewed. The mainly used islanding detection techniques may be classified as active and passive techniques. Passive techniques don’t perturb the system but they have larger nondetection zones, whereas active techniques have smaller nondetection zones but they perturb the system. In this paper a new hybrid method is propose...
متن کامل