Power-frequency magnetic field calculation around an indoor transformer substation
نویسندگان
چکیده
The authors propose a full three-dimensional (3D) calculation model based on a multipole technique able to predict the magnetic field pollution outside of indoor medium voltage/low voltage (MV/LV) transformer substations. The authors demonstrate that the proposed model may be advantageously used in all problems related to the characterization of the electromagnetic environment around a MV/LV transformer substation. They also show how the model may be used to support the optimised design of the cabin layout when this solution is sufficient to assure the reduction (below the exposure limits fixed by law) of the magnetic flux density in target volumes within civil buildings. In particular, the proposed algorithm has been applied to evaluate the magnetic flux density levels in the neighbourhood of a typical indoor MV/LV cabin placed at ground zero of a civil building (and therefore bordering on houses and/or offices). In addition, in order to mitigate the magnetic field outside the transformer substation, using the proposed calculation code an attempt was made to design the layout of the cabin by rearranging the position of the LV distribution switchboard (i.e., the power center, PC).
منابع مشابه
Some Aspects of Magnetic Shielding of a Transformer Substation Using Alternative Shielding Techniques
SUMMARY The paper investigates efficiency of different shielding techniques. The study was performed on the basis of 3-D substation model design where the finite-element method for calculation of magnetic fields (the EMAS software) was used and measurements were performed. The study was designed to meet the following objectives: − to obtain a useful analytical tool for evaluation of magnetic fi...
متن کاملAnalysis on the Shielding Effect of the Power Transformer Tank
The MV/LV transformer without a tank in the underground substation can produce remarkable interference with the computer Cathode-Ray Tube (CRT) displayers above the ground, because of the generated power frequency magnetic field. To resolve such problem, a tank with high conductivity or/and high permeability is needed to enclose the transformer. To evaluate the shielding effectiveness, the fini...
متن کاملSimulation Study on Ventilation & Cooling for Main Transformer Room of an Indoor Substation
Based on natural ventilation design scheme for main transformer room of an indoor substation, different air distribution schemes were obtained by changing height and size of air inlets and outlets. Three-dimensional simulation of air distribution was conducted for the transformer room by using Computational Fluid Dynamics (CFD) method. Ventilation & cooling effect of different indoor ventilatio...
متن کاملPower Frequency Magnetic Field Survey in Indoor Power Distribution Substation in Egypt
In our modern society electricity is vital to our health, safety, comfort and well-being. While our daily use of electricity is often taken for granted, public concern has arisen about potential adverse health effects from electric and magnetic – electromagnetic – fields (EMFs) produced by our use of electricity. This paper aims to compare between the measured magnetic field values and the simu...
متن کاملResearch on Proximity Magnetic Field Influence in Measuring Error of Active Electronic Current Transformers
The principles of the active electronic current transformer (ECT) are introduced, and the mechanism of how a proximity magnetic field can influence the measuring of errors is analyzed from the perspective of the sensor section of the ECT. The impacts on active ECTs created by three-phase proximity magnetic field with invariable distance and variable distance are simulated and analyzed. The theo...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
عنوان ژورنال:
دوره شماره
صفحات -
تاریخ انتشار 2005