Impact of Bridge type Fault Current Limiter on Power System Transient Stability
نویسندگان
چکیده
In this paper, transient stability improvement using bridge type fault current limiter (FCL) is presented in single machine infinite bus (SMIB) system with a double circuit transmission line. Three single-phase sets of the proposed FCL are installed at the beginning of feeder. The proposed FCL inserts an inductance and a resistance in the fault current pass. The insertion inductance and resistance not only limits the fault current level in an acceptable value but also improves transient stability of power system by consuming excessive energy of synchronous generator during fault. To reach maximum transient stability, the optimal resistor value of the proposed FCL is calculated. Analytical analysis and simulation results using PSCAD/EMTDC software are presented to show the current limiting future and transient stability enhancement using the proposed FCL in SMIB. Keywords-transient stability improvement; fault current limiter; optimal resistor; semiconductor switch.
منابع مشابه
RETRACTED! Transient stability enhancement of DFIG based 10 MW wind farm by using of new inductive bridge type fault current limiter
RETRACTED
متن کاملInfluence of Fault Current Limiter in Voltage Drop and TRV Considering Wind Farm
Influence of distributed generation systems in the distribution systems can increase the level of short-circuit current. The effectiveness of distributed generation systems is affected by the size, location, type of distributed generation systems technology, and the methods of connecting to distribution systems. Wind turbine system is the examples of distributed generation source. Not only does...
متن کاملSelection of Resistive and Inductive Superconductor Fault Current Limiters Location Considering System Transient Stability
Superconductor fault current limiter (SFCL) is an effective device to suppress high fault currents. This paper presents a comparative study of resistive and inductive fault current limiters from transient stability point of view. Appropriate location and type of the limiters in a HV substation is selected by a qualitative approach based on the equal area criterion. Study system is simulated by...
متن کاملThe Impact of Superconducting Fault Current Limiter Locations on Voltage Sag in Power Distribution System
In this paper, the impacts of installing superconducting fault current limiter (SFCL)in radial and loop power distribution system are evaluated to improve voltage sag in both cases of with and without distributed generations (DG). Among various SFCLs, the hybrid type with a superconducting element in parallel with a current limiting reactor (CLR) is selected. This is more effective than resisto...
متن کاملTransient stability augmentation of PV/DFIG/SG-based hybrid power system by parallel-resonance bridge fault current limiter
This paper proposes a parallel-resonance bridge type fault current limiter (PRBFCL) to augment the transient stability of a hybrid power system consisting of a photovoltaic (PV) power generation source, a doubly-fed induction generator (DFIG)-based wind energy system, and a synchronous generator (SG). The PRBFCL is designed such a way that it can provide sufficient damping characteristics to th...