Generalized-impedance and Stability Criterion for Grid-connected Converters
نویسندگان
چکیده
The output impedance matrix of a grid-connected converter plays an important role in analyzing system stability. Due to the dynamics of the DC-link control and the phase locked loop (PLL), the output impedance matrices of the converter and grid are difficult to be diagonally decoupled simultaneously, neither in the dq domain nor in the phase domain. It weakens the effectiveness of impedance-based stability criterion (ISC) in system oscillation analysis. To this end, this paper innovatively proposes the generalized-impedance based stability criterion (GISC) to reduce the dimension of the transfer function matrix and simplify system small-signal stability analysis. Firstly, the impedances of the converter and the grid in polar coordinates are formulated, and the concept of generalized-impedance of the converter and the grid is put forward. Secondly, through strict mathematical derivation, the equation that implies the dynamic interaction between the converter and the grid is then extracted from the characteristic equation of the grid-connected converter system. Using the proposed method, the small-signal instability of system can be interpreted as the resonance of the generalized-impedances of the converter and the grid. Besides, the GISC is equivalent to ISC when the dynamics of the outer-loop control and PLL are not considered. Finally, the effectiveness of the proposed method is further verified using the MATLAB based digital simulation and RT-LAB based hardware-in-the-loop (HIL) simulation.
منابع مشابه
A Generalized-Impedance Based Stability Criterion for Three-Phase Grid-Connected Voltage Source Converters
1 Abstract—The output impedance matrices of three-phase grid-connected voltage source converters (VSCs) are widely used in power system stability analysis. Regardless of how the impedance is modeled, there always exist coupling terms in the impedance matrix, which makes the system a multi-input-multi-output (MIMO) system. As a practical approximation, the coupling terms are generally omitted ...
متن کاملApplication of the Min-Projection and the Model Predictive Strategies for Current Control of Three-Phase Grid-Connected Converters: a Comparative Study
This paper provides a detailed comparative study concerning the performance of min-projection strategy (MPS) and model predictive control (MPC) systems to control the three-phase grid connected converters. To do so, first, the converter is modeled as a switched linear system. Then, the feasibility of the MPS technique is investigated and its stability criterion is derived as a lower limit on th...
متن کاملControl of Inverter-Interfaced Distributed Generation Units for Voltage and Current Harmonics Compensation in Grid-Connected Microgrids
In this paper, a new approach is proposed for voltage and current harmonics compensation in grid-connected microgrids (MGs). If sensitive loads are connected to the point of common coupling (PCC), compensation is carried out in order to reduce PCC voltage harmonics. In absence of sensitive loads at PCC, current harmonics compensation scenario is selected in order to avoid excessive injection of...
متن کاملStability Improvement of Grid-connected Converter with LCL Filter based on Capacitor Current Active Damping by Computational Delay Reduction
Nowadays, LCL filters utilization to suppress the grid-connected inverter switching harmonics is expanding and various methods such as capacitor current active damping scheme could be investigated to damp out these harmonics. However, the computational delays including control system, and PWM switching delays have significant effect on damping system stability. In most of LCL filter parameter d...
متن کاملModeling and Analysis of Harmonic Resonance Involving Renewable Energy Sources
The resonance between power-factor-correction capacitors and the line reactance is a common cause for harmonic problems in traditional power systems. Grid-connected inverters integrating renewable energy sources into the grid exhibit capacitive output impedance at harmonic frequencies and may also resonate with the grid impedance. In addition to possible amplification of current and voltage ...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید
ثبت ناماگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید
ورودعنوان ژورنال:
- CoRR
دوره abs/1706.05625 شماره
صفحات -
تاریخ انتشار 2017