Analysis of a Large Grounding System and Subsequent Field Test Validation Using the Fall of Potential Method
نویسندگان
چکیده
This paper examines various aspects of the design process and subsequent field test measurements of a large and complex substation grounding system. The study and measurements show that soil layering and lead interference can have a significant impact on the appropriate test location that yields the exact substation ground impedance. Applying a specific percentage rule such as the 61.8% rule for uniform soils to obtain the true ground impedance may lead to unacceptable errors for large grounding systems. This poses significant problems when attempting to validate a design based on raw test data that are interpreted using approximate methods to evaluate substation ground impedance, and determine ground potential rise (GPR), touch and step voltages. Advanced measurement methodologies and modern software packages were used to obtain and effectively analyze fall of potential test data, compute fault current distribution, and evaluate touch and step voltages for this large substation. Fault current distribution between the grounding system and other metallic paths were computed to determine the portion of fault current discharged in the grounding system. The performance of the grounding system, including its GPR and touch and step voltages, has been accurately computed and measured, taking into account the impedance of the steel material used of the ground conductors and circulating currents within the substation grounding system.
منابع مشابه
Application of Electromagnetic Field Theory to Measure Correct Grounding System Impedance: A Parametric Analysis
Measurement of the grounding system impedance of a substation or power plant is often required immediately after construction, in order to verify that the design calculations correctly predict the performance of the system. Years later, new measurements are sometimes required to check that the performance of the grounding system has not deteriorated. This type of measurement, however, which is ...
متن کاملBack-flashover Investigation of HV Transmission Lines Using Transient Modeling of the Grounding Systems
The article presents the transients analysis of the substation grounding systems and transmission line tower footing resistances which can affect to the back-flashover (BF) or overvoltage across insulator chain in an HV power systems by using EMTP-RV software. The related transient modeling of the grounding systems is based on a transmission line (TL) model with considering the soil ionization....
متن کاملLarge-scale Inversion of Magnetic Data Using Golub-Kahan Bidiagonalization with Truncated Generalized Cross Validation for Regularization Parameter Estimation
In this paper a fast method for large-scale sparse inversion of magnetic data is considered. The L1-norm stabilizer is used to generate models with sharp and distinct interfaces. To deal with the non-linearity introduced by the L1-norm, a model-space iteratively reweighted least squares algorithm is used. The original model matrix is factorized using the Golub-Kahan bidiagonalization that proje...
متن کاملطراحی بهینه، ایمن و اقتصادی سیستم زمین پستهای فشارقوی
Due to both safety and economic issues, exhaustive and optimal design of the grounding system of high voltage substations is one of the most important, expensive, sensitive, and complicated problems of the high voltage substations. In this paper, a novel designing method is proposed which consist of seven fundamental steps. The method is based on the ANSI/IEEE Std. 80-2000 standard. Most of the...
متن کاملImpact of Ocean-Land Mixed Propagation Path on Equivalent Circuit of Grounding Rods
In this paper, the effect of ocean-land mixed propagation path on the lightning performance of grounding rods is investigated. This effect is focused on two problems. The first is extracting exact equivalent circuit of grounding rods in the presence of oceans. The equivalent circuit can be used in transient analysis of power systems in the neighboring oceans. In the second one, this effect on t...
متن کامل