Staged-Fault Testing of Distance Protection Relay Settings
نویسندگان
چکیده
In order to analyze the operation of the protection system during induced fault testing in the Croatian power system, a simulation using the CAPE software has been performed. The CAPE software (Computer-Aided Protection Engineering) is expert software intended primarily for relay protection engineers, which calculates current and voltage values during faults in the power system, so that relay protection devices can be properly set up. Once the accuracy of the simulation model had been confirmed, a series of simulations were performed in order to obtain the optimal fault location to test the protection system. The simulation results were used to specify the test sequence definitions for the end-to-end relay testing using advanced testing equipment with GPS synchronization for secondary injection in protection schemes based on communication. The objective of the end-to-end testing was to perform field validation of the protection settings, including verification of the circuit breaker operation, telecommunication channel time and the effectiveness of the relay algorithms. Once the end-to-end secondary injection testing had been completed, the induced fault testing was performed with three-end lines loaded and in service. This paper describes and analyses the test procedure, consisting of CAPE simulations, end-to-end test with advanced secondary equipment and staged-fault test of a three-end power line in the Croatian transmission system.
منابع مشابه
Considering Pilot Protection in the Optimal Coordination of Distance and Directional Overcurrent Relays
The aim of the relay coordination is that protection systems detect and isolate the faulted part as fast and selective as possible. On the other hand, in order to reduce the fault clearing time, distance protection relays are usually equipped with pilot protection schemes. Such schemes can be considered in the distance and directional overcurrent relays (D&DOCRs) coordination to achieve faster ...
متن کاملA new interval approach for setting the distance relay zones to achieve perfect selectivity and maximum sensitivity
In this paper, an interval approach is presented to achieve perfect selectivity and maximum sensitivity in distance relay zones, considering uncertainties. For this purpose, first, the uncertainties affecting the settings of the three zones of a distance relay are discussed. Then, by using the Monte-Carlo simulation, the uncertainties are modelled and the impedances seen by the distance relay a...
متن کاملA new interval approach for setting the distance relay zones to achieve perfect selectivity and maximum sensitivity
In this paper, an interval approach is presented to achieve perfect selectivity and maximum sensitivity in distance relay zones, considering uncertainties. For this purpose, first, the uncertainties affecting the settings of the three zones of a distance relay are discussed. Then, by using the Monte-Carlo simulation, the uncertainties are modelled and the impedances seen by the distance relay a...
متن کاملEffects of CT and VT Connection Point on Distance Protection of Transmission Lines with FACTS Devices
This paper presents the effects of instrument transformers connection points on the measured impedance by distance relays in the presence of Flexible Alternating Current Transmission System (FACTS) devices with series connected branch. Distance relay tripping characteristic itself depends on the power system structural conditions, pre-fault operational conditions, and especially the ground ...
متن کاملDistance protection closed-loop testing using RTDS
This paper presents a distance protection test procedure by applying the Real-Time Digital Simulator (RTDS) of a power system. RTDS is a tool to design, develop, and test power-system protection. The RTDS enables real-time computation of electromagnetic phenomena with a calculation time step of even 50μs. The hardware allows the import and export of many signals from the simulator to an ext...