Negative effect of high pH on biocidal efficacy of copper and silver ions in controlling Legionella pneumophila.
نویسندگان
چکیده
Copper-silver (Cu-Ag) ionization has effectively controlled Legionella spp. in the hot water systems of numerous hospitals. However, it was ineffective at controlling Legionella in one Ohio hospital despite the confirmation of adequate total concentrations of copper and silver ions. The pH of the water at this hospital was found to be 8.5 to 9.0. The purpose of this study was to investigate the impact of pH and other water quality parameters, including alkalinity (HCO3-), hardness (Ca2+ and Mg2+), and amount of dissolved organic carbon (DOC), on the control of Legionella by Cu-Ag ionization. Initial concentrations of Legionella and copper and silver ions used in batch experiments were 3 x 10(6) CFU/ml and 0.4 and 0.08 mg/liter, respectively. Changes in bicarbonate ion concentration (50, 100, and 150 mg/liter), water hardness (Ca2+ at 50 and 100 mg/liter; Mg2+ at 40 and 80 mg/liter), and level of DOC (0.5 and 2 mg/liter) had no significant impact on the efficacy of copper and silver ions in killing Legionella at a neutral pH. When the pH was elevated to 9 in these experiments, copper ions achieved only a 10-fold reduction in the number of Legionella organisms in 24 h, compared to a millionfold decrease at pH 7.0. Silver ions were able to achieve a millionfold reduction in 24 h at all ranges of water quality parameters tested. Precipitation of insoluble copper complexes was observed at a pH above 6.0. These results suggest that pH may be an important factor in the efficacy of copper-silver ionization in controlling Legionella in water systems.
منابع مشابه
CONTROLLING LEGIO!NELIA IN HOSPITAL WATERSYSTEMS: EXPERIENCE WITH THE SUPERHEAT-AND-FLUSH METHOD AND COPPER-SaVER IONIZATION
ORJECI1VE: To evaluate the effect of copper-silver ionization on Legionella colonization and nosocomial legionnaires' disease and to compare the efficacy of metal ions versus the superheat-and-tlush method of disinfection. DESIGN: Prospective determination over a 36-month period of copper and silver ion concentrations in the recirculating hotwater system, Legionella colonization of the hospital...
متن کاملThe Different Antibacterial Impact of Silver Nanoparticles Against Legionella pneumophila Compared to Other Microorganisms
Legionella pneumophila is the pathogen responsible for severe pneumonia known as Legionnaires’ disease. Legionella can live under varied stress conditions, especially in cold environments, and is common in many artificial environments. In this study, the antimicrobial activity of biogenic silver nanoparticles, prepared using the culture supernatant of Klebsiella pneumoniae, was evaluated agains...
متن کاملIn vitro efficacy of copper and silver ions in eradicating Pseudomonas aeruginosa, Stenotrophomonas maltophilia and Acinetobacter baumannii: implications for on-site disinfection for hospital infection control.
Pseudomonas aeruginosa, Stenotrophomonas maltophilia and Acinetobacter baumannii are major opportunistic waterborne pathogens causing hospital-acquired infections. Copper-silver ionization has been shown to be effective in controlling Legionella colonization in hospital water systems. The objective was to determine the efficacy of copper and silver ions alone and in combination in eradicating P...
متن کاملThe Legionella pneumophila GIG operon responds to gold and copper in planktonic and biofilm cultures
Legionella pneumophila contaminates man-made water systems and creates numerous exposure risks for Legionnaires' Disease. Because copper/silver ionization is commonly used to control L. pneumophila, its mechanisms of metal response and detoxification are of significant interest. Here we describe an L. pneumophila operon with significant similarity to the GIG operon of Cupriavidus metallidurans....
متن کاملIntermittent use of copper-silver ionization for Legionella control in water distribution systems: a potential option in buildings housing individuals at low risk of infection.
One copper-silver ionization system was sequentially installed onto the hot-water recirculation lines of two hospital buildings colonized with Legionella pneumophila, serogroup 1. A third building with the same water supply and also colonized with Legionella served as a control. Four weeks after activation of the system, distal site positivity for Legionella in the first test building dropped t...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید
ثبت ناماگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید
ورودعنوان ژورنال:
- Applied and environmental microbiology
دوره 68 6 شماره
صفحات -
تاریخ انتشار 2002