Insulation Fault Diagnosis in High Voltage Power Transformers by Means of Leakage Flux Analysis
نویسندگان
چکیده
Power transformers in service are subjected to a wide variety of electrical, mechanical and thermal stresses capable of producing insulation faults. This type of failure figures amongst the most costly faults in distribution networks since it produces both machine outage and electrical supply interruption. Major research effort has therefore focused on the early detection of faults in the insulating systems of large high voltage power transformers. Although several industrial methods exist for the on-line and off-line monitoring of power transformers, all of them are expensive and complex, and require the use of specific electronic instrumentation. For these reasons, this paper will present the On-Line analysis of transformer leakage flux as an efficient alternative for assessing machine integrity and detecting the presence of insulating failures during their earliest stages. An industrial 400 kVA–20 kV/400V transformer will be used for the experimental study. Very cheap, simple sensors, based on air core coils, will be used to measure the leakage flux of the transformer, and non-destructive tests will also be applied to the machine in order to analyse preand post-failure voltages induced in the coils.
منابع مشابه
Characterization of Power Transformer Electromagnetic Forces Affected by Winding Faults
Electromagnetic forces in power transformer windings are produced by interaction between the leakage fluxes and current passing them. Since the leakage flux distribution along the windings height is in two axial and radial directions, so the electromagnetic forces have two components, radial and axial. There is a risk that a large electromagnetic force due to the short circuit or inrush current...
متن کاملA Novel Flux-Based Protection Scheme for Power Transformers
Internal Turn-Turn faults (TTF) are the most common failures in power transformers, which could seriously reduce their life expectancy. Although common protection schemes such as current-baseddifferential protection are able to detect some of the internal faults, some other minor ones (such as TTFs andshort circuit near the neutral point) cannot be detected by such schemes. Likewise, these rela...
متن کاملFault Diagnosis of Power Transformer Based on Gas Characteristic Analysis
Power transformers are one of the most critical devices in power systems. It is responsible for voltage conversion, power distribution and transmission, and provides power services. Therefore, the normal operation of the transformer is an important guarantee for the safe, reliable, high quality and economical operation of the power system. It is necessary to minimize and reduce the occurrence o...
متن کاملGenetic Programming Based Polynomial Networks Model for Insulation Fault Diagnosis of Power Transformers
A Genetic Programming based Polynomial Networks Model (GPPNM) is presented in this paper to promote the diagnostic performance of incipient insulation fault of power transformers. Other than conventional hierarchical architecture to build polynomial networks, the proposed GPPNM constructs it using tree-like structure of Genetic Programming (GP). By means of flexible selection of low-order polyn...
متن کاملDSP Based On-line Partial Discharge Monitoring System for High Voltage Power Cable
In high voltage power cable system, partial discharge (PD) is a common phenomenon which reflects the degradation of insulation. When partial discharge happens inside the cable, leakage current will flow through the grounded conductor. To couple the partial discharge current, one feasible and effective method is placing a clamp-on high frequency current transformer around the grounded strap. In ...
متن کامل