On-line Partial Discharge Monitor System of XLPE Power Cable Based on Virtual Instrument
نویسندگان
چکیده
High voltage XLPE power cable is a very important part of power system. The degree of electric-tree aging in the cable can be estimated effectually by measuring partial discharge. An on-line partial discharge monitor system of XLPE power cable was developed based on the virtual instrument designing conception. This system has the advantage of wide analog bandwidth, excellent anti-interference ability, good stability, powerful analysis, friendly interface, convenient operation, etc, it can detect the quantity of partial discharge (PD) in XLPE power cable. It holds utility value in power system.
منابع مشابه
On-line Partial Discharge Monitoring System and Data Processing Using WTST-NST Filter for High Voltage Power Cable
Defects inside insulation of HV XLPE cable accessories can lead to partial discharge (PD) activity. When PD activity happens, leakage current may flow through the grounded line. To acquire the PD current signal, one practicable and effective method is placing a high frequency current transformer (HFCT) winding the grounded line. In order to measure the insulation degradation, a partial discharg...
متن کاملA Novel Anti-interference Method for Partial Discharges On-line Measurement of Hv Power Cables
In order to extract the millivolt range partial discharge(PD) signals drown in the harsh electromagnetic interference for HV power cables, this paper presents a novel antiinterference method, based on fast fourier transform autothresholding method, 1-D discrete wavelet thresholding method and three phase amplitude and arrive-time difference method. This method is examined and proved to be effec...
متن کاملThe Application of Partial Discharge Detection for the condition assessment of XLPE Power Cables
Partial discharge (PD) detection is an important means in the condition-based maintenance of high voltage apparatus including crosslinked polyethylene (XLPE) power cables. In this contribution, we introduce the recent work in Shanghai municipal electric power company on the condition-based maintenance of XLPE power cables. As to how to carry out the PD detection in different circumstances, thre...
متن کاملDSP Based On-line Partial Discharge Monitoring System for High Voltage Power Cable
In high voltage power cable system, partial discharge (PD) is a common phenomenon which reflects the degradation of insulation. When partial discharge happens inside the cable, leakage current will flow through the grounded conductor. To couple the partial discharge current, one feasible and effective method is placing a clamp-on high frequency current transformer around the grounded strap. In ...
متن کاملThe Propagation of Partial Discharge Pulses in a High Voltage Cable
Partial discharge within the dielectric of HV solid dielectric power cable greatly shortens the cable life. It is desirable to detect and locate the PD in the cable before breakdown occurs. Understanding the phenomena of propagation of the PD pulse in a power cable is fundamental to the detection and location of PDs. In this paper a power cable model represented by a coaxial transmission lossle...
متن کامل