Transformer Modeling Based on Standard Frequency Response Measurements
نویسندگان
چکیده
High frequency models of large power transformers are required for analysis of transient interaction phenomena between transformers and the power system. Fast transient overvoltages may lead to transformer dielectric failures. Deeper understanding of the mechanisms may help to take actions against possible damages. This paper describes the simulation principle of transient interaction in matters of a transformer in several steps discriminating between internal and external aspects of simulation and analysis. The three main approaches of transformer high frequency modelling, black box, white box and grey box are compared and two different measurement strategies are discussed. An impedance estimation which is based on standard frequency response measurements was successfully tested with two distribution transformers. Index Terms Power Transformer, Transients, Modelling, Vector Fitting, Frequency Response Measurement, Black box, White box, Grey box
منابع مشابه
Classification of transformer faults using frequency response analysis based on cross-correlation technique and support vector machine
One of the most important methods for transformers fault diagnosis (especially mechanical defects) is the frequency response analysis (FRA) method. The most important step in the FRA diagnostic process is to differentiate the faults and classify them in different classes. This paper uses the intelligent support vector machine (SVM) method to classify transformer faults. For this purpose, two gr...
متن کاملA Feasible Solution to Distinguish the Transformer Winding Deformation from Insulation Characteristic Impacts on FRA Spectrum
Frequency Response Analysis (FRA) is popular technique which has been used since the last decade as a diagnostic method for transformers. However, accurate interpretation of FRA measurements is still challenging. Recent studies reveal that apart from winding deformation, FRA data can also be influenced by moisture variation in transformer paper insulation. Hence, a specific transformer’s model ...
متن کاملPower Auto-transformer Mechanical Faults Diagnosis Using Finite Element based FRA
Frequency response analysis (FRA) is a sensitive method established for testing the mechanical integrity of transformers. However, interpretation of FRA signature still needs expert opinions and there is no FRA interpretation code generally accepted. Various mechanical faults with different extents on power transformers are required to aid FRA interpretation. To address this challenge, in...
متن کاملEstimation of Moisture in Transformer Insulation Using Dielectric Frequency Response Analysis by Heuristic Algorithms
Transformers are one of the most valuable assets of power systems. Maintenance and condition assessment of transformers has become one of the concerns of researchers due to huge number of transformers has been approached to the end of their lifetimes. Transformer’s lifetime depends on the life of its insulation and the insulation’s life is strongly influenced by its moisture attraction as well....
متن کاملModeling the Frequency Response Movements in Power Transformers for Predicting Purposes
Power transformers are key components in electrical power supplies and their failure could cause severe consequences on continuity of service and also generates substantial costs. Identifying problems at an early stage, before catastrophic failure occurs, is a great benefit for reliable operation of power transformers. Frequency Response Analysis (FRA) is a new, well-known and powerful diagnost...