Grey Relational Analysis for Insulation Condition Assessment of Power Transformers Based Upon Conventional Dielectric Response Measurement
نویسندگان
چکیده
Conventional dielectric response measurement techniques, for instance, recovery voltage measurement (RVM), frequency domain spectroscopy (FDS) and polarization–depolarization current (PDC) are effective nondestructive insulation monitoring techniques for oil-impregnated power transformers. Previous studies have focused mainly on some single type of dielectric measurement method. However, the condition of oil paper insulation in transformer is affected by many factors, so it is difficult to predict the insulation status by means of a single method. In this paper, the insulation condition assessment is performed by grey relational analysis (GRA) technique after carefully investigating different dielectric response measurement data. The insulation condition sensitive parameters of samples with unknown insulation status are extracted from different dielectric response measurement data and then these are used to contrast with the standard insulation state vector models established in controlled laboratory conditions by using GRA technique for predicting insulation condition. The performance of the proposed approach is tested using both the laboratory samples and a power transformer to demonstrate that it can provide reliable and effective insulation diagnosis.
منابع مشابه
Estimation of Moisture in Transformer Insulation Using Dielectric Frequency Response Analysis by Heuristic Algorithms
Transformers are one of the most valuable assets of power systems. Maintenance and condition assessment of transformers has become one of the concerns of researchers due to huge number of transformers has been approached to the end of their lifetimes. Transformer’s lifetime depends on the life of its insulation and the insulation’s life is strongly influenced by its moisture attraction as well....
متن کاملPerformance Test of Power Transformer Prior to Maintenance Using DGA and Grey Relational Analysis
The insulation of power transformer i.e. oil and paper decomposition recognized by means of dissolved gas-in-oil analysis (DGA). To detect incipient faults in a transformer, standard key gas method of DGA is employed on the basis of quantity of gases released from the oil. This primary information also reflects the overall condition of a transformer. In this paper, condition assessment of power...
متن کاملReview of Modern Diagnostic Techniques for Assessing Insulation Condition in Aged Transformers
Cellulosic paper and oil insulation in a transformer degrade at higher operating temperatures. Degradation is accelerated in the presence of oxygen and moisture. Power transformers being expensive items need to be carefully monitored throughout its operation. Well established time-based maintenance and conservative replacement planning is not feasible in a current market driven electricity indu...
متن کاملPower transformers health index calculation using reliability methods for the case study of the Dez Dam and Karkheh Dam hydro power plants
Transformers in power plants act as intermediaries between the power plant and the power grid, which are affected by electrical stresses such as switching, thermal stresses such as overload and arc, and chemical reactions in the dielectric oil. Acid and moisture components cause deterioration of transformer oil and paper insulation. Condition assessment of transformers is a method to predict an...
متن کاملDielectric Response and Partial Discharge Diagnostics of Insulation Systems by Utilizing High Voltage Impulses
In this thesis, power system transients are considered as an opportunity for development of online diagnostics of power components and specifically the insulation systems of power transformers and bushings. Failures of power components and outages can lead to a huge economical loss in the electric power grid. Therefore reliable operation of power grid requires on-line monitoring and diagnostics...
متن کامل