Detection of Partial Discharges in Power Transformers using UHF PD Measurements and Acoustic Measurements
نویسندگان
چکیده
For examination and diagnostics of the insulation quality of high voltage devices the measurement of partial discharge (PD) is accomplished. The conventional PD measurement according to IEC60270 is in some situations not sensitive enough because of the high interference level in field. The development of an unconventional measuring method using electromagnetic probes is presented. These probes are inserted in the transformer tank during full operation via an oil valve normally used for oil filling. Due to the shielding characteristics of the transformer tank external electromagnetic disturbances are minimized and enable measurements with high signal-to-noise ratio. New experiences made in measurements in laboratory and in field lead to modified UHF PD probes. The newly developed probes have to be tested on their mechanical and electrical properties. For the functional test of UHF probes the Performance Check is presented. Taking a further step from the Performance Check to a Sensitivity Check which may in future allow an approximation of the PD quantity comparable to the apparent charge is discussed. Experiences with the UHF PD Measurement in the field are presented. Furthermore the method of PD localisation by combining UHF measurements with acoustic measurements are shown.
منابع مشابه
بررسی عملکرد پروبهای UHF در آشکارسازی تخلیه جزئی در ترانسفورماتورهای فشار قوی
Recently, UHF partial discharge (PD) detection on power transformers attracts lots of attentions. For the transformers already installed in power network, the UHF signals can be captured only by UHF probes installed through oil drain valve. Although UHF probes are commercially produced, there are a lot of missing information on characteristics and features of these probes for PD detection. In t...
متن کاملCombined In-Oil Sensor for Vibration Measurement and Partial Discharge Detection using Acoustic and Electromagnetic Emissions SEBASTIAN COENEN Siemens AG Germany
Common acoustic partial discharge (PD) and vibration measurements use sensors attached on the outside tank wall of (power) transformers. Hereby, tank structure can lead to severe signal damping which in practice often leads to acoustic PD signals below noise level. Scope of the work is an acoustic and ultra-high frequency (UHF) detection of PD and additional recording of transformer vibrations ...
متن کاملInvestigations of In-oil Methods for Pd Detection and Vibration Measurement
Usually, acoustic partial discharge (PD) and vibration measurements take place on the outside tank wall of power transformers. This contribution determines new approaches for acoustic PD measurements within the oil volume of the transformer combined with electromagnetic in-oil measurements. Scope of the work is an acoustic and ultra-high frequency (UHF) detection of PD and additional recording ...
متن کاملUhf and Acoustic Partial Discharge Localisation in Power Transformers
The reliability of electrical energy networks depends on the quality and availability of electrical equipment like power transformers. Local failures inside their insulation may lead to catastrophic breakdowns and can cause high outage and penalty costs. Beside the strength and type of a PD, the geometric PD position is of major interest concerning risk evaluation of the flaw. Conventional PD m...
متن کاملClassification of Acoustic Emission Based Partial Discharge in Oil Pressboard Insulation System Using Wavelet Analysis
Insulation used in transformer is mostly oil pressboard insulation. Insulation failure is one of the major causes of catastrophic failure of transformers. It is established that partial discharges (PD) cause insulation degradation and premature failure of insulation. Online monitoring of PDs can reduce the risk of catastrophic failure of transformers. There are different techniques of partial d...
متن کامل