A Transformer Partial Discharge Measurement System Based on Fluorescent Fiber
نویسندگان
چکیده
Based on the physical phenomena of optical effects produced by the partial discharge (PD) and on the characteristics of fluorescent fiber sensing of weak fluorescent signals, a PD measurement system using a fluorescent fiber sensor was designed. The main parameters of the sensing system were calculated, an experimental testing platform for PD simulation in the lab was established, and PD signals were then detected through ultra-high frequency (UHF) and optical methods under a needle-plate discharge model. PD optical pulses in transformer oil contained signal-peak and multi-peak pulse waveforms. Compared with UHF detection results, the number of PD pulses and the elapsed PD pulse phase time revealed a good corresponding relationship. However, PD signal amplitudes presented the opposite, thus indicating that PD UHF signals reflected pulse amplitude value, whereas PD optical signals reflected pulse energy magnitude. The n-u-φ three-dimensional distributions indicated that most of the PD signals concentrated in the nearby industrial frequency voltage peak value. Overall, the proposed fluorescent fiber sensing system design can be used successfully in transformer PD signal detection.
منابع مشابه
An Optic Fiber Sensor for Partial Discharge Acoustic Detection
AN OPTIC FIBER SENSOR FOR PARTIAL DISCHARGE ACOUSTIC DETECTION by Xiaodong Wang Partial discharge (PD) is a very common problem in operating power transformers and is one of the factors that could lead to failure of power transformers, leading to power outage and expensive repairs. The acoustic wave induced by PD can be measured and used for monitoring, diagnosing, and locating potential failur...
متن کاملDetection and Position Location of Partial Discharges in Transformers Using Fiber Optic Sensors
Power transformers are one of the most important components in the electrical energy network. Extending transformer life is very economically valuable due to power outage. Therefore the development of instruments to monitor the transformer condition is of great interest. Detection of partial discharges (PDs) in power transformers is an effective diagnostic because it may reveal and quantify an ...
متن کاملAn ultra-sensitive optical MEMS sensor for partial discharge detection
A diaphragm-based interferometric fiber optical microelectromechanical system sensor with high sensitivity is designed and tested for on-line detection of the acoustic waves generated by partial discharges (PD) inside high-voltage power transformers. In principle, the sensor is made according to Fabry Perot interference, which is placed on a micro-machined rectangular silicon membrane as a pres...
متن کاملOn-line Monitoring System Based on Principle of Electro-acoustic Monitoring for Transformer Partial Discharge
Partial discharge inside a transformer is mainly responsible for the insulation aging and damage of the transformer. However, partial discharge is usually accompanied by external signals like sound, light and electrical signals and detectable physical phenomena such as characteristical gas and dielectric loss. Therefore, it is of great significance to monitor online the external signals and phe...
متن کاملAnalysis and Location of Partial Discharges in Power Transformers by Means of Electrical Methods
Considering the number of failures in high voltage power transformers caused by problems in bushing and winding insulation, it is important to study means for diagnosing incipient failures, to avoid long unavailability periods and its consequences. The aim of this work is to study detection and measurement procedures, concerning the evaluation of position of partial discharge inside the transfo...
متن کامل