Performance Analysis of an Updraft Tower System for Dry Cooling in Large-Scale Power Plants

نویسندگان

  • Haotian Liu
  • Justin Weibel
  • Eckhard Groll
  • Ray W. Herrick
  • George Tsatsaronis
چکیده

An updraft tower cooling system is assessed for elimination of water use associated with power plant heat rejection. Heat rejected from the power plant condenser is used to warm the air at the base of an updraft tower; buoyancy-driven air flows through a recuperative turbine inside the tower. The secondary loop, which couples the power plant condenser to a heat exchanger at the tower base, can be configured either as a constant-pressure pump cycle or a vapor compression cycle. The novel use of a compressor can elevate the air temperature in the tower base to increases the turbine power recovery and decrease the power plant condensing temperature. The system feasibility is evaluated by comparing the net power needed to operate the system versus alternative dry cooling schemes. A thermodynamic model coupling all system components is developed for parametric studies and system performance evaluation. The model predicts that constant-pressure pump cycle consumes less power than using a compressor; the extra compression power required for temperature lift is much larger than the gain in turbine power output. The updraft tower system with a pumped secondary loop can allow dry cooling with less power plant efficiency penalty compared to air-cooled condensers.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Effect of Wind on Thermal Performance of Heller Dry Cooling Tower

In a steam power plant, the temperature of the cooling water leaving the condenser for recyclingshould decrease. This is achieved in a cooling tower. The Heller cooling tower does not require waterfor operation, thus, it is a suitable system for use in thermal power plants throughout Iran. Wind is anenvironmental factor that unfavorably affects the performance of a cooling tower. Previous studi...

متن کامل

Numerical and Analytical Study of Natural Dry Cooling Tower in a Steam Power Plant

Design of a natural dry cooling tower has been accomplished in two sections: the design of heat exchangers and the numerical solution of flow through the tower. Heat exchanger (Heller type) has been simulated thermodynamically and then coupled with a computer program, which calculated the turbulent natural convection flow through the tower. The computer program developed for this purpose can be...

متن کامل

Numerical and Analytical Study of Natural Dry Cooling Tower in a Steam Power Plant

Design of a natural dry cooling tower has been accomplished in two sections: the design of heat exchangers and the numerical solution of flow through the tower. Heat exchanger (Heller type) has been simulated thermodynamically and then coupled with a computer program, which calculated the turbulent natural convection flow through the tower. The computer program developed for this purpose can be...

متن کامل

Study of Degradation of Dry Cooling Tower Performance under Wind Conditions and Method for Tower Efficiency Enhancement (RESEARCH NOTE)

Wind affects adversely the cooling tower thermal performance. A field investigation was carried out to study the thermal performance of Heller cooling towers under wind conditions, involving measurement of wind velocity and its direction around the cooling tower, and obtaining water flow rates and temperatures at the cooling tower inlet and outlet. Results show that air suction at the tower top...

متن کامل

A Comprehensive Approach to an Optimum Design and Simulation Model of a Mechanical Draft Wet Cooling Tower

The present paper describes the designing of a thermally and economically optimum mechanical draft counter-flow wet cooling tower. The design model allows the use of a variety of packing materials in the cooling tower toward optimizing heat transfer. Once the optimum packing type is chosen, a compact cooling tower with low fan power consumption is modelled within the known design variables....

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

عنوان ژورنال:

دوره   شماره 

صفحات  -

تاریخ انتشار 2017