Study of Aging Characteristics of Generator Stator Insulation Based on Temperature Spectrum of Dielectric Dissipation Factor
نویسندگان
چکیده
In this paper, accelerated multi-factor aging tests in laboratory have been conducted on the stator ham of a large generator. During the period of aging, the temperature spectra of dielectric dissipation factor tan 6 of stator insulation were employed to investigate aging characteristics of insulation materials. Test results showed that the peak temperature T,,, of the tan 6 -T curve under 0.2U. shifts to higher temperature with aging time. At the same time, the gradient of the peak decreased with aging time and the peak even disappeared in the measurement range of temperature finally. It was suggested that temperature spectra of dielectric dissipation factor tan 6 of stator insulation could be used to estimate the aging condition of large generator stator insulation.
منابع مشابه
Improvement of Stator Slot Structure based on Electro-Thermal Analysis in HV Generator
High voltage generators are being subject to higher voltage rating and are being designed to operate in harsh conditions. Stator windings are the main component of generators in which Electrical, magnetically and thermal stresses remain major failures for insulation degradation accelerated aging. A large number of generators failed due to stator winding problems, mainly insulation deterioration...
متن کاملImprovement of Stator Slot Structure based on Insulation Stresses Analysis in HV Generator
High voltage generators are being subject to higher voltage rating and are being designed to operate in harsh conditions. Stator windings are the main component of generators in which Electrical, magnetical and thermal stresses remain major failures for insulation degradation accelerated aging. A large number of generators failed due to stator winding problems, mainly insulation deterioration. ...
متن کاملStudy of the Impact of Initial Moisture Content in Oil Impregnated Insulation Paper on Thermal Aging Rate of Condenser Bushing
This paper studied the impact of moisture on the correlated characteristics of the condenser bushings oil-paper insulation system. The oil-impregnated paper samples underwent accelerated thermal aging at 130 ̋C after preparation at different initial moisture contents (1%, 3%, 5% and 7%). All the samples were extracted periodically for the measurement of the moisture content, the degree of polym...
متن کاملOn the Feasibility of Using Poles Computed from Frequency Domain Spectroscopy to Assess Oil Impregnated Paper Insulation Conditions
Frequency Domain Spectroscopy (FDS) is an effective tool allowing assessing the condition of oil-paper insulation system in power equipment. However, results from these measurements are known to be greatly influenced by various parameters, including insulation aging, moisture content, and insulation geometry/volume, together with environmental condition such as temperature. In this contribution...
متن کاملSensitivity Assessment of Lightning Protection Device Aging Effect on Distribution Substation Insulation
Insufficient electrical endurance of equipment and insulation failure against overvoltage is one of the most effective reasons for failure the power line. Lightening, switching or other disruptive parameters can cause line outage or distribution substation failure. There are different devices used to improve the safety, reliability, and power quality of the system. Surge arresters are one of t...