MINLP Optimization of Cooling Towers

نویسندگان

  • Medardo Serna-González
  • José M. Ponce-Ortega
  • Arturo Jiménez-Gutiérrez
  • Nicolás de Hidalgo
چکیده

This paper presents a mixed-integer nonlinear programming (MINLP) model for the optimal design of mechanical counter-flow cooling towers, subjected to standard design constraints. The objective function consists of the minimization of the total annual cost, which includes the capital cost of the cooling tower (that depends on the filling material and the air flowrate) and the operating cost (that includes the costs for the water makeup and for the power consumed by the tower fan). Merkel’s method is used to set the dimensions of the tower, and empirical correlations are used to estimate mass transfer coefficients for the packed section of the tower. The design variables to be optimized are the water-to-air flow ratio, the water flow rate, the water inlet and outlet temperatures, the operating temperature approach, the type of packing, the type of draft, the volume of packing material, the total pressure drop due to the air flow rate, the fan power, and the water consumption. The MINLP model was solved with the GAMS software package using the DICOPT solver. The performance of the proposed model is shown with six examples. From the results of the examples, it can be observed that cooling towers with low temperature approaches are not suitable because driving forces become a limiting factor. On the other hand, dry-bulb temperature variations have a negligible effect on the tower size. From the set of design parameters analyzed, the temperature approach is shown to be a critical factor for the optimal design of cooling towers.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Online Optimal Operation Planning and Control of Cogeneration Systems

This paper proposes on-line optimal operation planning and control of cogeneration systems (CGS). CGS is usually connected to various facilities such as refrigerators, reservoirs, and cooling towers. In order to generate optimal operation planning for CGS, startup/shutdown status and/or input/output values of the facilities for each control interval should be determined. The facilities may have...

متن کامل

Particle Swarm Optimization for Optimal Operational Planning of a Cogeneration System

This paper proposes optimal operational planning for cogeneration system (CGS) using particle swarm optimization (PSO). CGS is usually connected to various facilities such as refrigerators, reservoirs, and cooling towers. In order to generate optimal operational planning for CGS, startup/shutdown status and/or input/output values of the facilities for each control interval should be determined....

متن کامل

Optimal Short-Term Scheduling of Multi-Chiller Plants Considering Energy Requirement of Cooling Towers, Pumps and Chillers

During extremely hot summer days, air conditioning systems are known as major electricity consumers in residential, commercial and industrial sectors. Moreover, high energy requirement of multiple-chiller plants may cause an interconnected power grid be faced with annual on-peak electrical demand, load-generation mismatch, voltage collapse and catastrophic wide area blackout. Therefore, this pa...

متن کامل

Effect of Ambient Condition on the Shower Cooling Tower in Four Type of Climates Condition

Water cooling by ambient takes place with two mechanisms of heat and mass transfer. Using packings at wet cooling towers has disadvantages such as obstruction, reduction of life expectancy and production of algae and fungi. In shower cooling towers types of towers packings are completely removed and water intake is in direct contact and heat transfer takes place in two ways of latent and sensib...

متن کامل

Particle Swarm Optimization for Optimal Operational Planning of a Cogeneration Plant

Recently, cogeneration systems (CGS) have been installed in various factories and buildings. CGS is usually connected to various facilities such as refrigerators, reservoirs, and cooling towers, and produces various energies for electric loads, air-conditioning loads, heating loads, and hot water loads (fig.1). Since daily load patterns of the various loads are different, optimal operational pl...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

عنوان ژورنال:

دوره   شماره 

صفحات  -

تاریخ انتشار 2008