Fault Current Characteristics of the DFIG under Asymmetrical Fault Conditions

نویسندگان

  • Fan Xiao
  • Xianggen Yin
  • Frede Blaabjerg
چکیده

During non-severe fault conditions, crowbar protection is not activated and the rotor windings of a doubly-fed induction generator (DFIG) are excited by the AC/DC/AC converter. Meanwhile, under asymmetrical fault conditions, the electrical variables oscillate at twice the grid frequency in synchronous dq frame. In the engineering practice, notch filters are usually used to extract the positive and negative sequence components. In these cases, the dynamic response of a rotor-side converter (RSC) and the notch filters have a large influence on the fault current characteristics of the DFIG. In this paper, the influence of the notch filters on the proportional integral (PI) parameters is discussed and the simplified calculation models of the rotor current are established. Then, the dynamic performance of the stator flux linkage under asymmetrical fault conditions is also analyzed. Based on this, the fault characteristics of the stator current under asymmetrical fault conditions are studied and the corresponding analytical expressions of the stator fault current are obtained. Finally, digital simulation results validate the analytical results. The research results are helpful to meet the requirements of a practical short-circuit calculation and the construction of a relaying protection system for the power grid with penetration of DFIGs.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Low Voltage Ride Through Enhancement Based on Improved Direct Power Control of DFIG under Unbalanced and Harmonically Distorted Grid Voltage

In the conventional structure of the wind turbines along with the doubly-fed induction generator (DFIG), the stator is directly connected to the power grid. Therefore, voltage changes in the grid result in severe transient conditions in the stator and rotor. In cases where the changes are severe, the generator will be disconnected from the grid and consequently the grid stability will be attenu...

متن کامل

Fault ride-through capability of a DFIG in isolated grids employing DVR and supercapacitor energy storage

In order to utilize Doubly Fed Induction Generators (DFIGs) as primary power source in an isolated system, they should be able to regulate the voltage and frequency of the system as well as ride-through faults. This paper proposes a new control strategy for a DFIG operating in an isolated power system, accomplished by a Dynamic Voltage Restorer (DVR) and a Supercapacitor Energy Storage System (...

متن کامل

Study on Fault Current of DFIG during Slight Fault Condition

In order to ensure the safety of DFIG when severe fault happens, crowbar protection is adopted. But during slight fault condition, the crowbar protection will not trip, and the DFIG is still excited by AC-DCAC converter. In this condition, operation characteristics of the converter have large influence on the fault current characteristics of DFIG. By theoretical analysis and digital simulation,...

متن کامل

Coordinated Control of a Doubly-Fed Induction Generator-Based Wind Farm and a Static Synchronous Compensator for Low Voltage Ride-through Grid Code Compliance during Asymmetrical Grid Faults

This paper aims to explore a viable solution for a doubly-fed induction generator (DFIG)-based wind farm to meet the reactive support requirement of the low voltage ride-through (LVRT) grid code with safe grid-connected operation during asymmetrical grid faults. First, the control scheme for the DFIG-based wind energy conversion system (WECS) is designed. Then, the controllability issue is anal...

متن کامل

Fault-Current Study of the Wind-Turbine-Driven Doubly-Fed Induction Generator with the Crowbar Protection

The crowbar protection is commonly used for wind turbines with a doubly-fed induction generator (DFIG) to enhance the low-voltage ride-through capability of the wind turbines. Thus, the fault-current characteristics of DFIG with the crowbar protection under symmetricand asymmetric-fault states are studied in this paper. Firstly, a DFIG dynamic model in the stator stationary reference frame is d...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

عنوان ژورنال:

دوره   شماره 

صفحات  -

تاریخ انتشار 2015