Reduction of Voltage Stress and Inrush Current of Power Transformers Using Controlled Switching
نویسنده
چکیده
Random energisation of power transformers often causes significant inrush currents and steep switching voltage wave fronts that are responsible for several adverse effects like huge current forces in the transformer windings, dielectric stress of the transformer winding insulation and temporary overvoltages. Controlled switching taking into account the residual flux is able to eliminate these inrush currents, but significant voltage wave fronts emerge from the switching action in almost all cases. Thus, a new algorithm is presented that extends the existing one so that a combined reduction of all stresses can be achieved. Systematic energisation studies were carried out in EMTPATP to calculate the optimal closing times of a three-legged 400 kVA transformer. Thereby, an inrush current peak of 1 pu will be tolerated so that the voltage wave front amplitude can be reduced. Depending on the strategy for controlled switching, the maximum voltage wave front amplitude of all phases can be limited to 0.75 pu (“Delayed Closing”, reduction of 11.7 %) respectively to 0.7 pu for “Rapid Closing” (reduction of 22 %).
منابع مشابه
Harmonic Modeling of Inrush Current in Core Type Power Transformers Using Hartley Transform
This paper presents a new method for evaluation and simulation of inrush current in various transformers using operational matrices and Hartley transform. Unlike most of the previous works, time and frequency domain calculations are conducted simultaneously. Mathematical equations are first represented to compute the inrush current based on reiteration and then Hartley transform is used to stud...
متن کاملMitigation Transformer Inrush Current Using Modified Transient Current Limiter
This study presents a modified transient current limiter (MTCL) for mitigation the inrush current of transformers. The MTCL is based on conventional transient current limiter (TCL), which, its configuration is modified to overcome the TCL drawbacks of operation. The proposed MTCL offers lower power losses and voltage/current THD during normal operation mode. It needs only one limiting reactor i...
متن کاملTransformer inrush current mitigation using controlled switching and magnetic flux shunts
The inrush current is a transient current that results from a sudden change in the exciting voltage across a transformer’s windings. It may cause inadvertent operation of the protective relay system and necessitate strengthening of the transformer’s mechanical structure. Many methods were reported in the literatures for reduction and mitigation of transformer inrush currents. This paper represe...
متن کاملTransient Transformer Inrush Currents due to Closing Time- and Residual Flux Measurement- Deviations if Controlled Switching is used
During energisation of power transformers, transient inrush currents with peaks up to the short-circuit current may arise. Using controlled switching taking into account the residual flux, the transients can – in theory – be eliminated completely. Real factors such as closing time scatter and residual flux measurement uncertainty have to be considered when checking the suitability of controlled...
متن کاملA NEURO-FUZZY TECHNIQUE FOR DISCRIMINATION BETWEEN INTERNAL FAULTS AND MAGNETIZING INRUSH CURRENTS IN TRANSFORMERS
This paper presents the application of the fuzzy-neuro method toinvestigate transformer inrush current. Recently, the frequency environment ofpower systems has been made more complicated and the magnitude of the secondharmonic in inrush current has been decreased because of the improvement of caststeel. Therefore, traditional approaches will likely mal-operate in the case ofmagnetizing inrush w...