A Performance of a Window Air Conditioner Using Alternative Refrigerants R22 AND R410A
نویسنده
چکیده
This paper presents the experimental performance analysis of a window air conditioner using two refrigerants R22 and R410A.The effect of the different parameters of performance analysis (refrigeration capacity, COP, compressor power ,pressure ratio ) were investigated for various evaporating temperature and ambient temperature. .The result shows that refrigerant R22 is better than R410A in case of COP, refrigeration capacity but for pressure ratio and compressor power R410A shows better performance than R22.Since R22 refrigerant has better performance than also this refrigerant is replaced by the end of 2015.Due to their severe environmental impact. NOMENCLATURE: COP : Coefficient of Performance ODP: Ozone Depletion Potential GWP : Global Warming Potential h : Specific Enthalpy (KJ/KG) M : Mass Flow Rate P: Pressure (KPA) PR : Pressure Ratio Q :Heat Transfer Rate (KW) T : Temperature Th: Thermometer EER : Energy Efficiency Ratio HC: Hydrocarbon HCFC : HydrochloroFluro Carbon TCond: CondenserTemperature (K)
منابع مشابه
Performance of R410A and R22 Low GWP Alternative Refrigerants at Elevated Ambient Temperatures
Growing concerns about the global warming impact of refrigerants used in HVAC&R equipment are driving development and evaluation of alternative refrigerants with lower global warming potentials (GWPs). The Air Conditioning, Heating, and Refrigeration Institute (AHRI) recently coordinated the Low-GWP Alternative Refrigerant Evaluation Program (AREP) in which commercial, university, and governmen...
متن کاملEvaluation of a Refrigerant R410A as Substitute for R22 in Window Air-conditioner
CFCs have been phased out, except for essential users, and HCFCs are to be eliminated by 2020, because of their ozone depletion potential. This generates a need for the investigation of zero ozone depletion potential (ODP) refrigerants or refrigerant blends. R410A is among newer brand of refrigerant blends, with zero ODP. The biggest difference to R22 is the pressure levels generated which are ...
متن کاملA Comparison Of An R22 And An R410A Air Conditioner Operating At High Ambient Temperatures
R22 and R410A split air-conditioning systems were tested and compared as outdoor temperature ranged from 27.8 °C (82.0 °F) to 54.4 °F (130 °F). The R410A system tests were extended to 68.3 °C (155.0 °F) ambient temperature with a customized compressor. Capacity and efficiency of both systems decreased linearly with increasing outdoor temperature, but the R410A system performance degraded more t...
متن کاملComparative Exergy Analysis of Vapor Compression Refrigeration System Using Alternative Refrigerants
Abstract—In present paper, the performance of various alternative refrigerants is compared to find the substitute of R22, the widely used hydrochlorofluorocarbon refrigerant in developing countries. These include the environmentally friendly hydrofluorocarbon (HFC) refrigerants such as R134A, R410A, R407C and M20. In the present study, a steady state thermodynamic model (includes both first and...
متن کاملLubrication Analysis of Rotary Compressors for HFC Refrigerants
In this study, a practical numerical analysis has been developed in order to investigate the lubrication characteristics between a rolling piston and a crank of rotary compressors. This analysis is treated as a coupled problem of the momentum equations and the Reynolds equation of oil film. Using this analysis, the lubrication characteristics between the rolling piston and the crank for 2-cylin...
متن کامل